Group setting parameters – Basler Electric BE1-851 Modbus Protocol User Manual

Page 46

Advertising
background image

3-8 BE1-851

Modbus

Protocol

9289900992 Rev F

Read: To read a value other than ASCII character ‘X’, the Select Output register must be
the most recent control register written AND must have been written within the previous
30 seconds.

P if Pulse Output selection has been made.
0 if Latch Output at 0 selection has been made.
1 if Latch Output at 1 selection has been made.
L if programmable Logic selection has been made.
E if Enable All Outputs serial control has been made.
D if Disable All Outputs serial control has been made.
X if Output control not selected or control timer has expired

Write: The desired ASCII character.

P to select Pulsing Output.
0 to select Latching Output at 0.
1 to select Latching Output at 1.
L to select programmable Logic.
E to select Enabling All Outputs override control.
D to select Disabling All Outputs override control.

40140

Operate

Output

A

ASC(1)

40142

Operate

Output

1

ASC(1)

40144

Operate

Output

2

ASC(1)

40146

Operate

Output

3

ASC(1)

40148

Operate

Output

4

ASC(1)

40150

Operate

Output

5

ASC(1)

Read: Current control.

P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
L to select programmable Logic.

D if All Outputs override control Disabled

Write: The desired ASCII character to alter control (corresponding Select register must
contain same value, written within previous 30 seconds).

P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
L to select programmable Logic.
E to Enable All Outputs override control.

D to Disable All Outputs override control.


∗ Requires an additional write of ‘Y’ to Exit register 40001 to allow these control settings to be saved to
the relay’s internal EEPROM (if Modbus

™ password security is enabled).

† 243 and 343 are not available when style option 1 is V or W.

Group Setting Parameters

40269-70

50TP

Pickup

FP

40273-74

50TN

Pickup

FP

40277-78

50TQ Pickup (250TN, Sensing input “G”)

FP

40281-82

150TP

Pickup

FP

40285-86

150TN

Pickup

FP

40289-90

150TQ Pickup (350TN, Sensing input “G”)

FP

Read and Write:

0.50 to 150.00 amps (5A units)


40271-72

50TP

Time

Delay

LI

40275-76

50TN

Time

Delay

LI

40279-80

50TQ Time Delay (250TN, Sensing input “G”)

LI