Global parameters, Control parameters – Basler Electric BE1-851 Modbus Protocol User Manual

Page 43

Advertising
background image

9289900992 Rev F

BE1-851 Modbus

Protocol

3-5

Note: Write to Report Selection and Report Focus to specify the report, which will be
made available via the Report (RPT) Template. The template is the Report Text Block at
47595-719.

Table 3-1. Report

Report Text

47595-719

Report Selection

40039

Report Focus

40040

RA-LGC Report

1

Not used

RA-MAJ Report

2

Not used

RA-MIN Report

3

Not used

RA-REL Report

4

Not used

RF Report

7

Not used

RF-# Report

8

Value of # (1 - 255)

RF-NEW Report

9

Not used

RS Report

10

Not used

RS-# Report

11

Value of # (1 - 255)

RS-NEW Report

12

Not used

RS-F# Report

13

Value of # (1 - 255)

Global Parameters

Global Parameter registers 40080 - 40099 are only for serial communication ports active with ASCII
protocol and for the Modbus

™ serial port, COM2, when Password Security register 40989 is enabled.

40080-83

Global

Password ASC(8)

40085-88

Setting

Password

ASC(8)

40090-93

Control

Password

ASC(8)

40095-98

Report

Password

ASC(8)

Read: If global access granted, password ASCII characters are read. Otherwise, the
ASCII character “

∗” is read.

Write: Password in ASCII character(s).
Note: If password written is less than 8 characters long, a binary zero value must be
included following the final password character.


40084

Global

Path

BM(8)

40089

Setting Path

BM(8)

40094

Control Path

BM(8)

40099

Report Path

BM(8)

Read: Path associated with password.
Write: Path associated with password.

Bit 2 is set for COM 2 access.
Bit 1 is set for COM 1 access.
Bit 0 is set for COM 0 / FP access.

Control Parameters

All values read from and written to Select and Operate registers are ASCII characters. Select registers
must be written first, followed by a write to the Operate register. A 30 second window starts after the first
write to the Select register. If the second write to the Operate register is not received within the 30-second
window, an error response will be returned.

Writes to Operate registers 40138, 40140 - 40150 with ASCII data ‘E‘ (Enable Output override control) or
‘D’ (Disable Output override control) requires an additional write of ‘Y’ to Exit register 40001 to allow these
control settings to be saved to the relay’s internal EEPROM.

NOTE

Do not use Control Parameter Registers interchangeably with the Legacy Control
Registers.