Fault template (flt) – Basler Electric BE1-851 Modbus Protocol User Manual

Page 60

Advertising
background image

3-22 BE1-851

Modbus

Protocol

9289900992 Rev F

Fault Template (FLT)

47514

Fault Date and Time - Day

INT

Read

only:

Any value (days since 01/01/1984).


47515-16

Fault Date and Time - Milliseconds

LI

Read

only:

0 to 86,399,999 milliseconds


47517

Fault

Event

Type BM(16)

Read

only:

Bit 0 for Breaker Fail
Bit 1 for Trip
Bit 2 for Logic
Bit 3 for Pickup
Bit 4 for Fault Record Trigger (Refer to Register 47492)

47518

Fault

Active

Group

SI

Read

only:

0 to 3


47519

Fault

Targets

MSBs

BM(16)

Read

only:

Bit 15 - BF
Bit 14 - 162
Bit 13 - 62
Bit 12 - 50TQ (250TN, Sensing input “G”)
Bit 11 - 50TN
Bit 10 - 50TC
Bit 9 - 50TB
Bit 8 - 50TA
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - 150TQ (350TN, Sensing input “G”)
Bit 3 - 150TN
Bit 2 - 150TC
Bit 1 - 150TB
Bit 0 - 150TA


47520

Fault

Targets

LSBs

BM(16)

Read

only:

Bit 15 - Spare
Bit 14 - 362

Bit 13 - 262

Bit 12 - 51Q (151N, Sensing input “G”)
Bit 11 - 51N
Bit 10 - 51C
Bit 9 - 51B
Bit 8 - 51A
BitS 7-0 - Spare

∗ 262 and 362 are available when style option 1 is V or W.

47524

Fault

Clearing

Time

Status

SI

Read

only:

0 if Valid Fault Clearing Time (Registers 47525-26) value

1 if No pickup

2 if N/A; Out of range