Register table, General, Conventions – Basler Electric BE1-851 Modbus Protocol User Manual

Page 21: Section 2, Register table -1

Advertising
background image

9289900992 Rev F

BE1-851 Modbus

Protocol

2-1

SECTION 2

REGISTER TABLE

MAPPING BE1-851 PARAMETERS INTO MODICON HOLDING REGISTER
ADDRESS SPACE

General

Parameters are mapped into the holding register address space (40001 - 49999) in blocks according to
access type.

Any Holding Register not listed in the Register Table is an unassigned Holding Register. A value of zero
always results when reading an unassigned Holding Register. Writes to unassigned Holding Registers
are legal, but no action will be taken (the write is ignored).

Conventions

The Data Format column uses the following abbreviations:

ASC(x) - ASCII string, where x = the maximum defined string length
BM(x) - Bit-map, where x = the number of related bits
FP

- Floating point

INT

- Integer (16-bit integer)

LI

- Long Integer (32-bit integer)

SI

- Short Integer (8-bit integer)

DP

- Double Precision (legacy BE1-851 only)

The Notes column uses the following abbreviations:

GRP

- Group Template Member

FLT

- Fault Template Member

RPT

- Report Template Member

NS

- Not Supported

TS

- Time Stamp format: MSEC of the day (0 to 86,400,000 ms) and days since 01/01/1984.

LEG

- Original (legacy) BE1-851 Modbus

™ parameter mapping.

PS

- Effective only when the Password Security parameter is enabled. See REGISTER DETAILS for

Password Security holding register 40989.

PW

- Effective for any communication port active with ASCII protocol and for the Modbus

™ port

(COM 2) when Password Security is enabled.