Basler Electric BE1-851 Modbus Protocol User Manual

Page 55

Advertising
background image

9289900992 Rev F

BE1-851 Modbus

Protocol

3-17

Bit 10 - Virtual Output 10 status
Bit 9 - Virtual Output 9 status
Bit 8 - Virtual Output 8 status
Bit 7 - Virtual Output 7 status
Bit 6 - Virtual Output 6 status
Bit 5 - Virtual Output 5 status
Bit 4 - Virtual Output 4 status
Bit 3 - Virtual Output 3 status
Bit 2 - Virtual Output 2 status
Bit 1 - Virtual Output 1 status
Bit 0 - Virtual Output A status


47370

System Status (Logic Var 48 to 63)

BM(16)

Read

only:

Bit 15 - Setting Group 3 active
Bit 14 - Setting Group 2 active
Bit 13 - Setting Group 1 active
Bit 12 - Setting Group 0 active
Bit 11 - Output 1 trip coil monitor
Bit 10 - Alarm minor
Bit 9 - Alarm major
Bit 8 - Alarm logic
Bit 7 - HMI reset key
Bit 6 - 101 slip contact
Bit 5 - 101 close
Bit 4 - 101 trip
Bit 3 - Input 4 status
Bit 2 - Input 3 status
Bit 1 - Input 2 status
Bit 0 - Input 1 status


47373

Current Active Group Setting

SI

Read only:

0 to 3


47374

Current

Group

Control

Setting

ASC(1)

Read

only:

ASCII character 0, 1, 2, 3, L

47375

Current Output Control Settings (OutputPulse0) MSBs

BM(16)

Read

only:

Bits 15 - 6 Spare
Bit 5 - Output 5 pulse low
Bit 4 - Output 4 pulse low
Bit 3 - Output 3 pulse low
Bit 2 - Output 2 pulse low
Bit 1 - Output 1 pulse low
Bit 0 - Output A pulse low

47376

Current Output Control Settings (OutputPulse1) LSBs

BM(16)

Read

only:

Bits 15 - 6 Spare
Bit 5 - Output 5 pulse high
Bit 4 - Output 4 pulse high
Bit 3 - Output 3 pulse high
Bit 2 - Output 2 pulse high
Bit 1 - Output 1 pulse high
Bit 0 - Output A pulse high