Group setting parameters, Global setting parameters – Basler Electric BE1-851 Modbus Protocol User Manual

Page 23

Advertising
background image

9289900992 Rev F

BE1-851 Modbus

Protocol

2-3

Holding

Read/Write

Data

Register Parameter

Supported

Format

Notes


40147

Select Output 4

R W

ASC(1)

40148

Operate Output 4

R W

ASC(1)

40149

Select Output 5

R W

ASC(1)

40150

Operate Output 5

R W

ASC(1)

∗ 243 and 343 are not available when style option 1 is V or W.

Group Setting Parameters

40269-70

50TP Pickup

R W

FP

GRP

40271-72

50TP Time Delay

R W

LI

GRP

40273-74

50TN Pickup

R W

FP

GRP

40275-76

50TN Time Delay

R W

LI

GRP

40277-78

50TQ Pickup (250TN, Sensing input “G”)

R W

FP

GRP

40279-80

50TQ Time Delay (250TN, Sensing input “G”)

R W

LI

GRP


40281-82

150TP Pickup

R W

FP

GRP

40283-84

150TP Time Delay

R W

LI

GRP

40285-86

150TN Pickup

R W

FP

GRP

40287-88

150TN Time Delay

R W

LI

GRP

40289-90

150TQ Pickup (350TN, Sensing input “G”)

R W

FP

GRP

40291-92

150TQ Time Delay (350TN, Sensing input “G”)

R W

LI

GRP


40305-06

51P Pickup

R W

FP

GRP

40307-08

51P Time Dial

R W

FP

GRP

40309-10

51P Curve Type

R W

ASC(3)

GRP

40311-12

51N Pickup

R W

FP

GRP

40313-14

51N Time Dial

R W

FP

GRP

40315-16

51N Curve Type

R W

ASC(3)

GRP

40317-18

51Q Pickup (151N, Sensing input “G”)

R W

FP

GRP

40319-20

51Q Time Dial (151N, Sensing input “G”)

R W

FP

GRP

40321-22

51Q Curve Type (151N, Sensing input “G”)

R W

ASC(3)

GRP


40359-60

62 Time Delay 1

R W

LI

GRP

40361-62

62 Time Delay 2

R W

LI

GRP

40363-64

162 Time Delay 1

R W

LI

GRP

40365-66

162 Time Delay 2

R W

LI

GRP

40367-68

262 Time Delay 1

∗ R

W

LI

GRP

40369-70

262 Time Delay 2

∗ R

W

LI

GRP

40371-72

362 Time Delay 1

∗ R

W

LI

GRP

40373-74

362 Time Delay 2

∗ R

W

LI

GRP


40406-07

79 First Automatic Reclose Delay

R W

LI

GRP

40408-09

79 Second Automatic Reclose Delay

R W

LI

GRP

40410-11

79 Third Automatic Reclose Delay

R W

LI

GRP

40412-13

79 Fourth Automatic Reclose Delay

R W

LI

GRP

40414-15

79 Reset Time Delay

R W

LI

GRP

40416-17

79 Reclose Fail Time Delay

R W

LI

GRP

40418-19

79 Maximum Reclose Time

R W

LI

GRP

40420

79 Sequence Control

R W

BM(16)

GRP

∗ 262 and 362 are available when style option 1 is V or W.

Global Setting Parameters

40606-07

Breaker Fail Time Delay

R W

LI


40608-09

Programmable 51 Curve Constant A

R W

FP

40610-11

Programmable 51 Curve Constant B

R W

FP

40612-13

Programmable 51 Curve Constant C

R W

FP

Advertising
This manual is related to the following products: