Register details, Introduction, Logic settings – Basler Electric BE1-851 Modbus Protocol User Manual

Page 39: Logic modes, Section 3, Register details -1

Advertising
background image

9289900992 Rev F

BE1-851 Modbus

Protocol

3-1

SECTION 3

REGISTER DETAILS

INTRODUCTION

This section details the register formats and data ranges of the previous section. The two sections
combined provide all information necessary to communicate with the BE1-851 Modbus

™ Holding

Registers.

Any Holding Register not listed in the Register Table is an unassigned Holding Register. A value of zero
always results when reading an unassigned Holding Register. Writes to unassigned Holding Registers
are legal, but no action will be taken (the write is ignored).

Logic Settings

Logic settings consist of a combination of modes, masks, terms, and term counts. Logic modes are
specific to each logic set, while the masks, terms, and term counts have value definitions consistent
throughout all logic sets. A single logic equation consists of a “mask” and “term” pair. The logic “term
count” is used only in VOA, VO1 - VO15 virtual output logic blocks.

The logic “mode” enables or disables the logic equation for that logic block.

The logic “mask” corresponds to the System Status bits to be evaluated. These bits are referenced in the
desired logic equation and are set to 1 (non-used bits masked out as 0‘s).

The logic “term” corresponds to the System Status bit’s TRUE or FALSE state referenced in the desired
logic equation where only the TRUE bits in the equation are set to 1.

The logic “term count” may be of one of four logic types which are NONE (logic disabled), OR only (a + b
+ c), AND only (a

∗ b ∗ c) or MIXED (a ∗ b + b ∗ c).

The following defines all logic set parameters:

Logic Modes

41505

Programmable 50TP Block Logic Mode

INT

41522

Programmable 50TN Block Logic Mode

INT

41539

Programmable 50TQ Block Logic Mode (250TN, “G”)

INT

41556

Programmable 150TP Block Logic Mode

INT

41573

Programmable 150TN Block Logic Mode

INT

41590

Programmable 150TQ Block Logic Mode (350TN, “G”)

INT

Read

and

Write:

0

for

disabled

1

for

enabled

41658

Programmable Breaker Failure Logic Mode

INT

Read

and

Write:

0

for

disabled

1

for

enabled

41691

Programmable

51P

Logic

Mode

INT

41708

Programmable

51N

Logic

Mode

INT

41725

Programmable 51Q Logic Mode (151N, “G”)

INT

Read and Write:

0 for disabled

1 for enabled

41844

Programmable 62 Timer Logic Mode

INT

41877

Programmable 162 Timer Logic Mode

INT

Read and Write:

0 for disabled

1 for Pickup/Dropout

2 for One-Shot Non-Retriggerable

3 for One Shot Retriggerable

Advertising