Basler Electric BE1-851 Modbus Protocol User Manual

Page 45

Advertising
background image

9289900992 Rev F

BE1-851 Modbus

Protocol

3-7

40135

Select 101 Virtual Breaker Control Switch

ASC(1)

Read: To read a value other than ASCII character ‘X’, the Select 101 Virtual Breaker
Control Switch register must be the most recent control register written AND must have
been written within the previous 30 seconds.

C if Close selection has been made.

T if Trip selection has been made.
X if 101 Virtual Breaker Control Switch control not selected or control timer has
expired

Write: The desired ASCII character.

C to select Closing the Switch.
T to select Tripping the Switch.


40136

Operate 101 Virtual Breaker Control Switch

ASC(1)

Read: Current control.

C if Close Switch.
T if Trip Switch.

Write: The desired ASCII character to alter control (corresponding Select register must
contain same value, written within previous 30 seconds).

C to Close Switch.
T to Trip Switch.


40137

Select

All

Outputs

ASC(1)

Read: To read a value other than ASCII character ‘X’, the Select All Output register must
be the most recent control register written AND must have been written within the
previous 30 seconds.

P if Pulse All Outputs selection has been made.

0 if Latch All Outputs at 0 selection has been made.

1 if Latch All Outputs at 1 selection has been made.

L if programmable Logic selection has been made.

E if Enable All Outputs override control has been set.

D if Disable All Outputs override control has been set.

X if All Outputs control not selected or control timer has expired.

Write: The desired ASCII character.

P to select Pulsing All Outputs.
0 to select Latching All Outputs at 0.
1 to select Latching All Outputs at 1.
L to select programmable Logic.
E to select Enabling All Outputs override control.
D to select Disabling All Outputs override control.

40138

Operate

All

Outputs

ASC(1)

Read: Current control.

E if All Outputs override control Enabled.
D if All Outputs override control Disabled.

Write: The desired ASCII character to alter control (corresponding Select register must
contain same value, written within previous 30 seconds).

P to Pulse All Outputs.
0 to Latch All Outputs at 0.
1 to Latch All Outputs at 1.
L to select programmable Logic.
E to Enable All Outputs override control.

D to Disable All Outputs override control.


40139

Select Output A

ASC(1)

40141

Select

Output

1

ASC(1)

40143

Select

Output

2

ASC(1)

40145

Select

Output

3

ASC(1)

40147

Select

Output

4

ASC(1)

40149

Select

Output

5

ASC(1)