Basler Electric BE1-851 Modbus Protocol User Manual

Page 51

Advertising
background image

9289900992 Rev F

BE1-851 Modbus

Protocol

3-13

Read

and

Write:

Bits 15 to 10 - Spare
Bit 9 - Changes Lost alarm
Bit 8 - Logic=None alarm
Bit 7 - Fault Record Time Out
Bit 6 - Virtual Output 15 alarm
Bit 5 - Virtual Output 14 alarm
Bit 4 - Virtual Output 13 alarm
Bit 3 - Setting Group Change Active alarm
Bit 2 - Loss of IRIG-B sync or IRIG-B decode problem
Bit 1 - An override is active in one or more outputs
Bit 0 - EEPROM Non-fatal error

41266

Major

Alarm

Mask

LSBs

BM(16)

41268

Minor

Alarm

Mask

LSBs

BM(16)

41270

Logic Alarm Mask LSBs

BM(16)

Read only:

Bit 15 - User settings changed, (‘EXIT’ with ‘Y’)
Bit 14 - Power reset alarm, hard reset of MPU
Bit 13 - Clock problem, real time clock has not been set
Bit 12 - Communicating failure alarm, read error on serial port
Bit 11 - Operating System Overload detected alarm
Bit 10 - Setting group override in effect
Bit 9 - Q demand alarm, excessive negative-sequence unbalance
Bit 8 - Neutral demand alarm
Bit 7 - Phase demand alarm
Bit 6 - Breaker alarm #3
Bit 5 - Breaker alarm #2
Bit 4 - Breaker alarm #1
Bit 3 - Recloser lockout alarm
Bit 2 - Recloser fail alarm
Bit 1 - Breaker fail alarm
Bit 0 - Trip Circuit Monitor alarm


41272

Clock

Format

-

Date

ASC(1)

Read

and

Write:

M for mm/dd/yy format

D for dd/mm/yy format


41273

Clock Format - Time

SI

Read

and

Write:

12 for 12 hour clock

24 for 24 hour clock


41274

Clock

Format

-

Daylight

Savings

SI

Read

and

Write:

0 for disabling Daylight Savings

1 for enabling Daylight Savings


41275

Phase

Demand

Interval

SI

41276

Neutral

Demand

Interval SI

41277

Negative-Sequence

Demand

Interval

SI

Read

and

Write:

1 to 60 minutes

0

to

disable

41284

Output

Hold

Mask

BM(8)

Read

and

Write:

Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Output 5 Status