Basler Electric BE1-851 Modbus Protocol User Manual

Page 44

Advertising
background image

3-6 BE1-851

Modbus

Protocol

9289900992 Rev F

40117

Select Group

ASC(1)

Read: To read a value other than ASCII character ‘X’, the Select Group register must be
the most recent control register written AND must have been written within the previous
30 seconds.

0 if Group 0 selection has been made.

1 if Group 1 selection has been made.

2 if Group 2 selection has been made.

3 if Group 3 selection has been made.

L if Logic selection has been made.

X if Group control not selected or control timer has expired

Write: the desired ASCII character.

0 to select Group 0.

1 to select Group 1.

2 to select Group 2.

3 to select Group 3.

L to select Logic.

40118

Operate

Group

ASC(1)

Read: Current control.

0 if Group 0.
1 if Group 1.

2 if Group 2.
3 if Group 3.
L if Logic.

Write: the desired ASCII character to alter control (corresponding Select register must

contain same value, written within previous 30 seconds).

0 to select Group 0.
1 to select Group 1.
2 to select Group 2.
3 to select Group 3.
L to select Logic.

40119

Select Virtual Selector Switch 43

ASC(1)

40121

Select Virtual Selector

Switch

143

ASC(1)

40123

Select Virtual Selector Switch 243 †

ASC(1)

40125

Select Virtual Selector Switch 343 †

ASC(1)

Read: To read a value other than ASCII character ‘X’, the Select Virtual Selector Switch
register must be the most recent control register written AND must have been written
within the previous 30 seconds.

P if Pulse Switch selection has been made.
0 if Latch Switch at 0 selection has been made.
1 if Latch Switch at 1 selection has been made.
X if Virtual Selector Switch control not selected or control timer has expired.

Write: The desired ASCII character.

P to select Pulsing the Switch.
0 to select Latching the Switch at 0.
1 to select Latching the Switch at 1.


40120

Operate Virtual Selector Switch 43

ASC(1)

40122

Operate Virtual Selector Switch 143

ASC(1)

40124

Operate Virtual Selector Switch 243 †

ASC(1)

40126

Operate Virtual Selector Switch 343 †

ASC(1)

Read: Current control.

P if Pulse Switch.
0 if Latch Switch at 0.
1 if Latch Switch at 1.

Write: The desired ASCII character to alter control (corresponding Select register must
contain same value, written within previous 30 seconds).

P to Pulse Switch.
0 to Latch Switch at 0.
1 to Latch Switch at 1.