Basler Electric BE1-851 Modbus Protocol User Manual

Page 49

Advertising
background image

9289900992 Rev F

BE1-851 Modbus

Protocol

3-11

Read

only:

0 - 300 baud (Do not select for Port 2 Modbus

™ communications.)

1 - 600 baud (Do not select for Port 2 Modbus

™ communications.)

2 - 1200 baud (Do not select for Port 2 Modbus

™ communications.)

3 - 2400 baud
4 - 4800 baud
5 - 9600 baud
6 - 19K baud


40972

Serial

Port

1

Relay

Address

INT

40981

Serial

Port

2

Relay

Address

INT

Read

and

Write:

0 to 65,534


40964

Serial Port 0 Software Flow Control

SI

40973

Serial Port 1 Software Flow Control

SI

Read

only:

0 if XON / XOFF Control is disabled
1 if XON / XOFF Control is enabled

40965

Serial

Port

0

Page

Length

SI

40974

Serial

Port

1

Page

Length

SI

Read

only:

0

for

disabled

1 to 40 for number of lines / page

40966

Serial

Port

0

Acknowledgement

Format

SI


40975

Serial

Port

1

Acknowledgement

Format

SI

Read:

0 if No acknowledge

1 if Acknowledge enabled

Write:
0

for

No

acknowledge

1 to 255 to enable acknowledge


40986

Serial Port 2 Modbus

™ Parity

SI

Read

and

Write:

0 for No parity
1 for Even parity
2 for Odd parity


40987

Serial Port 2 Modbus

Remote

Delay

SI

Read

and

Write:

1 to 20: 10 to 200 milliseconds


40988

Serial Port 2 Modbus

Stop

Bits SI

Read

and

Write:

1 for One stop bit

2 for Two stop bits


40989

Serial Port 2 Modbus

™ Password Security

SI

Read

and

Write:

0

for

Disable

Password

1 for Enable Password †


∗ When Password Security is disabled, no access is required (Access Password, Access Request, and
Exit holding registers has no effect) and no password protection is used. Global Parameters, holding
registers 40080 to 40099 (ASCII command GF-PW), have no effect on the Modbus

™ serial port, COM 2.