Herrmidifier Herrtronic MD User Manual

Page 10

Advertising
background image

Herrtronic

®

MD Series

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

10

www.herrmidifier-hvac.com

Controls

The Herrtronic MD Series Humidifier has the capability to utilize

one of three types of control schemes.

1. On/Off

2. Proportional

3. Proportional + Integral

Controls may be supplied by the factory or others. The following

information applies to all controls factory supplied or furnished

by others. All external electrical control circuits are to be con-

nected to the unit using the twelve pole terminal strip located

in the electrical compartment. The terminal strip is accessed

through the side electrical compartment door. Field wiring from

humidistat to humidifier and between safety devices, such as

high limit humidistat and air proving switches, should be 18

AWG stranded or 20 AWG solid wire. If conduit is not used with

the controls wiring, install the black plastic fingered bushing (in

accessory pack) and completely seal with RTV silicone.

Wall devices should be mounted at a height similar to that of a

typical thermostat and should be located in an area that will pro-

vide good representation of the overall space being humidified.

Do not mount wall devices directly in the air stream of a supply

grille or room distribution unit.

Duct control devices should be mounted in a location where the

humidity and temperature are uniform, usually the return duct.

Do not mount in front of the steam distributor or in a mixing,

turbulent, or isolated area.

Duct high limit devices should be mounted downstream of the

steam distributors-far enough that under normal conditions in

the air stream, the steam has been completely absorbed, typi-

cally 10 ft. The device should be located such that it can sense

humidified air as it approaches saturation. Do not mount in dead

air spaces such as inside of corners or erroneous operation may

result.

Air proving devices should be mounted so that they sense air

flow (or the absence of it). Wire the device so that it closes when

air flow is present and will open when there is no air flow. The

purpose of the device is to prove that air flow is present before

steam is distributed into the duct.

The following information and diagrams are shown for each con-

trol scheme. Please refer to the control scheme that your humid-

ifier was set up for and follow the diagram for control circuit con-

nections. The factory-set control type and signal are indicated

on a label adjacent to the controls terminal strip.

Control Circuit Connections

Mode 1 - ON/OFF Operation

1. Control Input - Unit will operate with any two position device

(See Fig. 9). Demand for humidity will close the contact.

2. Limit Input - Unit will operate with any two position device

(See Fig. 9). The humidistat contact will open on humidity

rise.

Mode 2 - Proportional Operation

1. If two position airflow and/or high-limit humidistat is used

wire as shown in Figure 9.

2. Control Input - Interpreted by the humidifier as a demand of

output signal. Input device should be linear. Unit can accept

any VDC or mADC signal within a range of 0-20 VDC or

mADC (See Fig. 10). Unit may also accept a resistive signal

0-135 ohms (See Fig. 11).

3. Limit Input - Unit may accept any modulating input within

the same ranges as the control inputs listed above.

a. Proportional VDC or mADC (See Fig. 12)

b. Resistive (See Fig. 13)

Additionally, a P + I sensor may be used as a limit

input.

c. VDC (See Fig. 16)

d. mADC (See Fig. 17)

1

2

3

4

5

Air Flow Switch

High Limit Stat

Control Humidistat

FIGURE 9

6

7

See Note Pg. 28

68.1 k Resistor

4

5

_

FIGURE 10

VDC or

mADC

Signal

+

4

5

6

_

FIGURE 11

W

+

R

B

OUT

FIGURE 12

_

8

9

+

VDC or

mADC

Signal

8

9

10

_

FIGURE 13

W

+

R

B

OUT

Advertising