Herrmidifier Herrtronic MD User Manual

Page 12

Advertising
background image

Herrtronic

®

MD Series

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

12

www.herrmidifier-hvac.com

Remote Alarm

The Herrtronic MD Humidifier is equipped with a remote alarm

output. It is a triac output that may be used to energize an exter-

nal relay or buzzer to indicate an alarm condition is present. The

alarm output is activated whenever an indicating fault condition

exists. When units are networked together, the master’s alarm

contacts will close if a fault occurs at either the master or one of

the slave units. The contacts are connected at poles 1 and 2 of

the remote alarm terminal strip 3.

In order to use the remote alarm output with a Building Manage-

ment System, the remote alarm output must be used to energize

a mechanical relay. The contacts of the external relay may then

be wired to an input on the BMS to indicate if an alarm condition

is present. The remote alarm output may not be used like a dry

contact to a BMS.

Do not exceed the contact specifications!

Contact rating:

• 24 VAC - 3.0 A

• 24 VDC - 2.1 A

Unit Networking

When networking units together in a master/slave configura-

tion, be sure to maintain polarity between poles 11 and 12 on

all units. Units are to be wired as a parallel circuit. More than

one branch is allowable so that the master unit can be centrally

located (See Fig. 19). A maximum of 29 slave PC boards (29

MDS or MDM units or 14 MDD units) may be configured as a

network. Included in each installation pack is a 120 ohm resistor.

This resistor should be inserted into R28 on the microprocessor

board (see Fig. 32) on the appropriate end units of the chain.

(Refer to Fig. 19)





















































































Advertising