NOTE

1. For On/Off (mode 1) units, a resistor (68.1 kohms) between poles 5 and 7 on the controls terminal strip is required.

(34.0 kohms for MDD units)

2. If more than one MDS, MDM or MDD are “networked” together, a resistor may be required in socket R28 on PCB.

(See pg.12)

J3

J1

J5

1

1

1

J4

1

2

SW7

RESE

T

EPR
OM

RAM

CR1

CR2

CR4

CR5

R16

R28

R12

R7

CONTACTOR IND.

FAULT IND.

SW5

SW6

SW4

SW3

SW1

SW2

Microprocessor Board

FILL VALVE IND.

DRAIN VALVE IND.

J1 MOLEX

CONNECTOR

J5 MOLEX

CONNECTOR

J3 MOLEX

CONNECTOR

HEAT SINK

CAPACITY RESISTOR

RESET

SWITCH

SELECT

RESISTORS

RIBBON CABLE

CONNECTOR

HIGH LIMIT RESISTOR

Circuit Board: J1 Connector

PIN

4 Toroid Input, Non-polar

3 Toroid Input, Non-polar

2 RS-485 Communication, Positive, Digital

1 RS-485 Communication, Negative, Digital

5 Not Used

Circuit Board: J3 Connector

PIN

1 Power Input, 24 VAC

2 Power Input, 24 RET (GND)

3 Not Used

4 24 VAC, for contractor coil, (Always)

5 24 VAC, for contractor coil, switched

6 Alarm Output

7 Alarm Output

8 VAC, for drain valve, (Always)

9 24 VAC, for drain valve, switched

10 24 VAC, for fill valve, (Always)

11 24 VAC, for fill valve, switched

Circuit Board: J5 Connector

PIN

11. Door interlock input, 24 VAC to operate

10 Air flow/High Limit input, 24 VAC to operate

9 Auxiliary contact input, 24 VAC when energized and 0

VAC when de-energized.

8 Cylinder Full input

7 +5 VDC

6 Limit input signal – Modulating

5 Limit input ground – Modulating

4 +20 VDC

3 +5 VDC

2 Control input signal – Modulating and On/Off

1 Control input ground – Modulating and On/Off

Circuit Board: J3 Connector

PIN

1-14

LCD, 2-Lines X 20 Characters, non-backlit

Figure 32