Herrmidifier Herrtronic MD User Manual

Page 23

Advertising
background image

Herrtronic

®

MD Series

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

23

www.herrmidifier-hvac.com

Unit Detected Faults (Red Light is Illuminated)

Problem / Symptom

Probable Cause

Reason - Correction

Overcurrent

When this condition occurs, the system

has sensed an excessive current draw

(138% of rated current) and has shut itself

down and drained completely to prevent

possible damage. The system has already

taken preventative action by attempting to

drain down prior to the fault condition oc-

curring. Therefore, further analysis is re-

quired before restart is attempted.

Restricted Drain System

Clean and replace as necessary

Use of softened water without adjusting

operating parameters

See Fig. 30

Water conductivity in excess of 750

micromho

See Fig. 30 and 31

Expired steam cylinder – a mineral bridge

has developed allowing a short between

two electrodes.

Replace steam cylinder

If drain tempering is enabled and the rate

of fill is exceeding the rate of draining,

the tank will fill whenever the unit tries to

drain.

Adjust the fill valve metering screw to

slow the rate of fill so the unit can drain

properly. See Fig. 21 for adjusting screw

location.

Fill System Fault

The unit has been in fill cycle for 15 min-

utes continuously without reaching re-

quired output or cylinder full. System will

shutdown and drain completely.

Restricted or blocked fill system (strainer,

solenoid, external shut-off valve.)
Partially or completely open drain valve.
Extremely low conductivity supply water

End of Cylinder Life

The cylinder is full and humidifier has not

been able to achieve desired output within

setpoint.

Cylinder expired-electrodes have been

consumed.

Replace

Extremely low conductivity supply water Add a 1/4 teaspoon of salt to the cylinder.

High Humidity

Humidity in the space being measured by

the control sensor has exceeded the pre-

set alarm level. This alarm is only avail-

able on units configured with P + I control

(mode 3).

Tampering with the control humidity set-

point.

1. Reset your alarm setpoint.

2. Turn off humidifier at main disconnect

until humidification season.

Alarm set-point too close to control set-

point
Humidifier is powered but not operating

and RH is above setpoint

Sensor or wiring has failed.

Low Humidity

Humidity in the space being measured

by the control sensor has dropped below

the preset alarm level. This alarm is only

available on units configured with P + I

control (mode 3).

Alarm setpoint too close to control set-

point

1. Turn the humidifier “on” to satisfy de-

mand.

2. Adjust the low humidity alarm.

Humidifier is powered but turned “off” and

the RH is below the alarm setpoint.
Sensor or wiring has failed

Slave Fault

One of the 6 indicating faults has been de-

tected in a slave unit.

Review of the slave units is required to

determine specific fault conditions.

Contactor Failed

Unit has tried to turn on but contactor has

not closed, or unit should be off, but con-

tactor is still closed.

Failed contactor - It’s common to find

metal chips or other construction debris

lodged in the contactor preventing proper

operation

Repair or replace

Faulty control wiring.
Auxiliary contact dislodged from proper

position.
Faulty auxiliary contact
Installation with RDU’s--the jumper be-

tween control terminal strip poles 1 & 2

needs to be removed.