No faults present in system slave xx has faults, Herrtronic, Md series – Herrmidifier Herrtronic MD User Manual

Page 19

Advertising
background image

Herrtronic

®

MD Series

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

19

www.herrmidifier-hvac.com

Diagnostics

The Herrtronic MD humidifier includes built-in diagnostics ca-

pability to identify potential problems, protect the system, and

minimize service/repair time. Should the system detect a critical

condition, a “fault” warning will be displayed on the LCD. Cer-

tain faults prompt immediate system shutdown to protect the

MD unit or ductwork. Other faults allow the unit to continue to

operate but alert the operator to potential problems that require

maintenance. Other faults, which are designed for initial system

tune-up or preventative maintenance, are classified as “non-in-

dicating.” These faults are viewed by pressing the “fault” key on

the control panel. The table reflects all of the faults the system

is capable of detecting. Please note, however, that certain faults

are unique to certain control modes or networked systems and

are only visible where applicable.

During operation, when an “indicating” fault occurs, the word

FAULT will be visible in the lower right hand section of the LCD.

The red fault light will also be illuminated.

If an “indicating” fault has been detected or a preventative check

is being performed, follow this procedure to determine the cause

of the fault:

1. The LCD must be in the MAIN MENU to access diagnos-

tics. Press “FAULT” key to determine the type of fault.

2. Press the up arrow to determine if there is more than one

fault.

3. If possible, correct the condition causing the fault signal or

plan corrective action.

4. Press “ENTER” to clear the fault signal from the display.

When “ENTER” is pressed, all faults registered in the unit

will be cleared. If the condition causing the fault is not cor-

rected, another fault signal will occur.

5. Under normal operating conditions, pressing the “FAULT”

button will prompt the following display:

In a multi-unit network, the master (“00”) unit will indicate a fault

within the entire network. To find the fault(s), follow steps 1 and

2 for the master unit. If the display indicates “No Faults Present

In System,” then neither the Master, nor any Slave unit, has any

faults.

If any slave has a fault, the LCD will read:

Utilize the communications (Menu 4) from the Master to access

the particular slave with fault(s) to determine the fault. (Refer to

communication instructions in the programming section). Press

the “up” arrow button to determine if there is more than one

“slave” that has a “fault.”

System Fault Conditions

(See Troubleshooting Section for corrective action)

Fault

Operation Status

Comments

Current Overload (4) Shutdown and Drain

Manual Reset(1)

138% of Capacity

Setpoint Exceeded

Contactor Failed (4)

Continued Operation Humidification Re-

quired

Cylinder Full Zero

Current

Continued Operation Humidification

re-

quired; unit not func-

tioning properly

Fill System Fault (4)

Shutdown and Drain

Manual Reset (1)

Fill for 15 min. – can-

not achieve capacity

setpoint or cyl. Full

Zero Electrode Cur-

rent

Continued Operation Humidification

re-

quired, no current

draw

Non-zero Slowly De-

creasing Amps

Continued Operation Defective drain sys-

tem

Non-zero Non-De-

creasing Amps

Continued Operation Defective drain sys-

tem

Non-zero Non- In-

creasing Amps

Continued Operation Defective fill system

Non-zero Slowly In-

creasing Amps

Continued Operation Defective fill system

Cylinder Full

Continued Operation Caused by low water

conductivity, foam-

ing, or end of cyl.

Life.

End of Cylinder Life

(4)

Continued Operation Cannot achieve ca-

pacity and on cylinder

full or programmed

duration

Air Flow / High Limit

System Shutdown,

Automatic Reset (2)

Insufficient airflow /

high limit setting ex-

ceeded

Hi Humidity Alarm (3)

(4)

Continued Operation Alarm threshold

achieved

Lo Humidity Alarm

(3)(4)

Continued Operation Alarm threshold

achieved

Humidity Sensor

Failed (3)

Continued Operation

unless both fail

Humidity less than

4% or greater than

100%

Slave “XX” Has Fault

(4)

Continued Operation

of Master

Slave has fault

Communication Port

Fault

Continued Operation

of Master

Slave operation un-

known

1.

Manual reset requires the problem be corrected and the unit turned “on” at

the keypad

2.

Automatic reset will resume normal operation once the circuit is closed.

3.

Proportional + Integral Control Only

4.

Indicating Fault

NO FAULTS PRESENT
IN SYSTEM

SLAVE XX HAS FAULTS

Advertising