Herrmidifier Herrtronic MD User Manual

Page 17

Advertising
background image

Herrtronic

®

MD Series

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

17

www.herrmidifier-hvac.com

Menu 5. Once hot water is being drained, check the follow-

ing:

• Steam condensing on the bottom of the cabinet.

Correct by lowering the drain line or adding DRAIN

TEMPERING.

• Flash steam entering the steam cylinder compart-

ment due to inadequate drain line.

• Flash steam entering the electrical compartment if

the knockout for the control wires isn’t sealed. This

should be sealed even if there doesn’t appear to be

any steam entering into the compartment. If conduit

is not used with the controls wiring, install black plas-

tic fingered bushing and completely seal with RTV

Silicone.

• Water must drain from unit freely. If there are restric-

tions in the drain line, it will send hot water/steam up

into the CABINET DRAIN and/or the OVERFLOW

TUBE which will pool inside the cabinet and could

leak out of the unit onto the floor.

START-UP IS COMPLETED. MAKE SURE CONTROLLING

DEVICES ARE SET FOR DESIGNED CONDITIONS. PRO-

CEED TO AND COMPLETE CHECK-LIST. AFTER INITIAL

WARM UP, SHUT UNIT DOWN, TURN OFF MAIN POWER

AND RECHECK TIGHTNESS OF POWER CONNECTIONS

WHILE UNIT IS WARM (TORQUE TO 15-20 in-lbs.).

Figure 21





















Advertising