I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

7

www.herrmidifier-hvac.com

3. Connect the ¾” tube from the accessory pack to the drain

reservoir. Cut hose to necessary length.

WARNING!

Be sure that the ¾” drain tube is not kinked or bent in a man-

ner to prevent free flowing drainage from the drain reservoir

to the drain pipe.

4. Insert the other end of the tube into a minimum 6” length of

1 ¼” minimum I.D. copper line. The balance of the drain

line should be 1” I.D. minimum with a minimum 1/8” per foot

slope. (See Figure 2)

WARNING!

If the drain line is exposed, it is recommended that it be in-

sulated for safety. Do not use PVC drain line unless “Drain

Tempering” is enabled (see page 16-17).

NOTE

Inlet water pressure must be in the range of 20-100 psig.

Consult the factory if you are outside this range. Softened wa-

ter may be used but requires that the low drain threshold be

adjusted (refer to Fig. 30 page 27). Drain water can be tem-

pered to lower its temperature (refer to page 16).

3/4" MIN. I.D./1" MAX O.D.

FLEXIBLE DRAIN CONNECTION

6" MIN. LENGTH OF 1-1/4" MIN. I.D.
COPPER LINE. IF PVC IS USED, LOCAL

CODES REQUIRE A LOWER TEMPERATURE

BALANCE OF DRAIN LINE TO BE 1" MIN. I.D.

WITH A MINIMUM PITCH OF 1/8" PER 12" OF RUN

DRAIN RESEVOIR

DRAIN WATER, ADD DRAIN TEMPERING.

4" RECOMMENDED

8"

RECOMMENDED

Figure 2