Herrmidifier Herrtronic MD User Manual

Page 27

Advertising
background image

Herrtronic

®

MD Series

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

27

www.herrmidifier-hvac.com

Inputs / Outputs of Terminal Strips and Terminal Block

Terminal Block

Position 1-6

24 RET (GND)

7-12

24 VAC

All twelve (12) positions should be utilized if the Room Dispersion Unit (RDU) is installed

RDU Terminal Strip – Connections to RDU only

Pole

1

24 RET (GND) (Always)

2

24 VAC Trigger (24 VAC when contactor is energized)

3

Line Voltage (Always)

4

Line Voltage (Always)

5

24 VAC Air (24 VAC when switch Proving Switch is closed)

6

24 VAC (Always)

Control Terminal Strip

Pole

1

24 VAC (Always)

2

Airflow / High Limit input, 24 VAC for operation

3

External “Off”, 24 VAC for operation

4

Control input ground – Modulating and on/off

5

Control input signal – Modulating and on/off

6

+5 VDC

7

+20 VDC

8

Limit input ground - Modulating

9

Limit input signal - Modulating

10

+5 VDC

11

RS-485 Communication, Negative, Digital

12

RS-485 Communication, Positive, Digital

Figure 30

Hard Water/Softened Water*

(750-1000 Micromho)

Adjust Menu Items to These Settings

MDM

MDS/

MDD

Cycle Time (Menu #3)

75

115

Low Drain Threshold (Menu #2)

88

84

Capacity Setpoint (Menu #2)

96

96

High Drain Threshold (Menu #3)

108

108

*Naturally soft water is less than 50 micromho.

Figure 31

Very Hard Water

(> 1000 Micromho)

Adjust Menu Items to These Settings

MDM

MDS/

MDD

Cycle Time (Menu #3)

60

100

Low Drain Threshold (Menu #2)

91

86

Capacity Setpoint (Menu #2)

94

92

High Drain Threshold (Menu #3)

105

105

Advertising