Maintenance

To maintain efficiency of the unit, the water level in the cylinder

will slowly rise as the electrodes become coated with minerals.

Progressively, the water level reaches the cylinder full electrode,

representing the maximum allowable water level. Eventually, all

of the usable electrode surfaces will be coated. After the end

of cylinder life setpoint has been reached, the LCD will read

“End of Cylinder Life” fault. Cylinder replacement should occur

to maintain satisfactory humidity levels. “End of Cylinder Life”

varies with water conductivity. Refer to the chart that follows:

Conductivity (micro-mhos)

(approximately)

Average Cylinder Life

(Hours)

70

2000

100

2000

135

1900

170

1800

250

1300

500

800

750

650

1000

500

NOTE

Many factors in addition to water conductivity effect cylinder

life. Total dissolved solids (TDS) and exact mineral content

of the water can have negative effects on cylinder life. Your

representative will be happy to review your water analysis.

If you don’t have an analysis and are on a municipal system,

the municipal water authority will provide one free of charge.

Conductivity between 70 and 200 micromho is best handled

with “on/off” control. Discuss your application with the factory

if your water is in this range and “Proportional” or “Propor-

tional + Integral” control is required. Water with less than 70

micromho may not be sufficient to allow the unit to operate.

Herrmidifier has considerable experience optimizing the per-

formance of your humidifier on “fringe” water conditions. Con-

sult your representative.

To Remove the Cylinder:

1. Turn the unit “off” by pressing the “on/off” button. Drain the

cylinder completely using the manual drain (Menu 5).

2. Disconnect the power to the unit..

3. Disconnect the electrode power wires (and jumpers if used)

- noting the orientation, and the cylinder full electrode wire

from the cylinder. Remove the expired cylinder from the

cabinet.

4. Position the new cylinder in the cabinet. Place the new “O”

ring as shown in Fig. 22. Lubricate the “O” ring with water

only and install cylinder into drain cup, EST-1062, pushing

down firmly with a twisting motion.

5. Reconnect the power wiring (and jumpers if required) refer-

ring to appropriate Figure on the next page that matches

the power wiring configuration of the unit. Be certain to use

lock washers on each electrode and tighten the electrode

knob (Fig. 25 or 29).

6. Installation is now complete, Reconnect power, turn unit

on, allow cylinder to fill and check for leaks. AFTER INI-

TIAL WARM UP, SHUT UNIT DOWN, TURN OFF MAIN

POWER AND RECHECK TIGHTNESS OF POWER CON-

NECTIONS WHILE UNIT IS WARM (TORQUE TO 15-20

in-lbs.).

Extended Shutdown:

The humidifier is set by the factory to drain if the unit doesn’t

operate for seven days. However, the drain time can be revised

through reprogramming (Refer to Page 14). Always drain the

cylinder completely if it will be off of an extended period of time

(see Auto drain feature, menu 2, page 13).