Herrmidifier Herrtronic MD User Manual

Page 26

Advertising
background image

Herrtronic

®

MD Series

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

26

www.herrmidifier-hvac.com

Summary of Troubleshooting Tips for the Inputs and Outputs of the EST-1250 Circuit Board

Turn power ON to the unit (green power light should be ON) & verify proper sensor installation. If all of the 24 VAC inputs to the

circuit board are energized, but ANY of the outputs from the circuit board are NOT indicated, the circuit board may not be operating

properly.

1) Verify that these inputs to the circuit board are energized:

24 VAC Input to Board

Source of 24 VAC Input to Board

At Connector J3 At Terminal Block

PIN 1, wire # 17

Terminal 10, wire # 17

PIN 4, wire # 18

Terminal 9, wire # 18

PIN 8, wire # 19

Terminal 8, wire # 19

PIN 10, wire # 20

Terminal 7, wire # 20

At Connector J5

At Terminal Strip

PIN 1, wire # 37

Terminal 3, wire # 16 (thru door interlock)

PIN 2, wire # 45

Terminal 2, wire # 45

At Connector J5

At Auxiliary contact

PIN 3, wire # 3

Wire # 3

2) Verify that these outputs from the circuit board are energized:

24 VAC Output from Board

Function of 24 VAC Output from Board

At Connector J3

PIN 5, wire # 34

Energize contactor coil, wire # 34

PIN 9, wire # 23

Energize drain solenoid, wire # 23

PIN 11, wire # 13

Energize fill solenoid, wire # 13

DC Output from Board

Function of DC Output from Board

At Connector J5

At Terminal Strip

5 VDC at PIN 5, wire # 5

5 VDC available at terminal #10, wire # 5

20 VDC at PIN 8, wire # 8

20 VDC to power sensors from terminal #7, wire # 8

5 VDC at PIN 9, wire # 9

5 VDC to simulate sensor input at terminal #6, wire # 9

Output to Unit Display

From Connector J4

Board generates clear and legible two line display instead of a single row of black or gray blocks.