I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

18

www.herrmidifier-hvac.com

4"

REC

OMMENDED

8"

REC

OMMENDED

POWER SUPPL

Y:

1. M

AT

CHES D

AT

A PLA

TE

2. IS PR

OPERL

Y GR

OUNDED

3. C

AN C

ARR

Y A

T LEAST 125%

OF R

ATE A

MP DR

AW

4. DISC

ONNEC

T SUPPLIED B

Y

O

THERS.

M

AKE SURE ALL HIGH

VOL

TA

GE

ELEC

TRIC

AL C

ONNEC

TIONS

ARE TIGHT

.

NO UNTR

APPED L

OW SPO

TS

IN STEA

M SUPPL

Y.

AIR FL

OW IS HORIZ

ONT

AL OR

VER

TIC

AL UPFL

OW

A SPECIAL PIPE IS REQUIRED FOR

VER

TIC

AL DOWNFL

OW

,

OR A

VER

TIC

AL DISTRIBUT

OR PIPE IN A HORIZ

ONT

AL

AIR FL

OW

.

M

AKE SURE ALL HIGH

VOL

TA

GE

ELEC

TRIC

AL C

ONNEC

TIONS ON

STEA

M C

YLINDER(S) ARE

TIGHT

(15-20 in/lbs)

3/4" MIN. I.D

./1" M

AX O

.D

.

FLEXIBLE DR

AIN C

ONNEC

TION

DURING FILL C

YCLE CHECK

TO SEE IF AN

Y

W

ATER IS DR

AINING FR

OM UNIT

. A L

O

T OF

W

ATER FL

OWING OUT OF

THE UNIT

WOULD

INDIC

ATE EX

CESSIVE

W

ATER PRESSURE

.

REDUCE

THR

OUGH ME

TERING FILL SOLENOID

OR SUPPL

Y

VAL

VE

TO HUMIDIFIER. A SM

ALL

A

MOUNT OF

W

ATER IS NO

T UNC

OMMON.

6" MIN. LENGTH OF 1-1/4" MIN. I.D

. C

OPPER LINE

.

IF PVC IS USED

, L

OC

AL C

ODES M

AY REQUIRE A L

OWER

TEMPER

ATURE DR

AIN

W

ATER.

THIS IS NO

T UNC

OMMON

AND DR

AIN

TEMPERING SHOULD BE ENABLED

.

BALANCE OF DR

AIN LINE

TO BE 1" MIN. I.D

.

WITH A MINIMUM PIT

CH OF 1/8" PER 12" OF RUN

KNOCK

OUT FOR C

ONTR

OL

WIRING MUST BE

SEALED

TO PRE

VENT FLASH STEA

M FR

OM

ENTERING ELEC

TRIC

AL C

OMP

AR

TMENT

.

PRE-ST

AR

TUP CHECKLIST