REMKO WKF 120 Duo User Manual

Page 23

Advertising
background image

Heat pump operating mode

Heat pumps can work in various operating modes.

Monovalent

The heat pump is the only heat generator for the

building all year round. This mode is particularly

suitable for heating plants with low inlet tempera-

tures and is primarily used in combination with

brine/water and water/water heat pumps.

Monoenergetic

The heat pump has an electrical heater to handle

peak loads. The heat pump covers the majority of

the required heating capacity. Occasionally, when

it is extremely cold outside, an auxiliary heater

switches on as required in order to support the

heat pump.

Bivalent alternative

The heat pump provides the entire heating energy

down to a predetermined outside temperature. If

the outside temperature drops below this value, a

second heat generator switches on, while the heat

pump switches off. There is a distinction to be

made here between alternative operation with oil-

or gas heat and regenerative operations with

solar energy or wood-fired heating. This mode is

possible for all heat distribution systems.

Layout

A precise calculation of the building's heating load

according to EN 12831 is required for the design

and dimensioning of a heating system. However,

approximate requirements can be determined

based on the year of construction and the type of

building. Table

Ä on page 24 shows the approx-

imate specific heating loads for a number of

building types. The required heating system output

can be calculated by multiplying the area to be

heated with the given values.

For a precise calculation, various factors must be

considered. The transmission-heat requirement,

the infiltration heat-loss and an allowance for water

heating comprise the total heating capacity which

the heating system must provide.

To determine the transmission heat requirement,

the surface areas of flooring, external walls, win-

dows, doors and roof are necessary. Likewise nec-

essary is information on the building materials

used, the different heat transfer coefficients (the

so-called U value). Also required are the room tem-

perature and the standard outside temperature,

that is, the lowest outside-temperature on average

that will occur during the year. The equation for

determining the transmission heat requirement is

Q=A x U x (t

R

-t

A

) and must be calculated individu-

ally for all room-enclosing surfaces.

The infiltration heat requirement takes into consid-

eration how often the heated room air is

exchanged for cold external air. The room volume

(V), the air exchange frequency (n) and the spe-

cific heat capacity (c) of the air is also required in

addition to the room temperature and standard out-

side temperature. The equation is: Q=V x n x c (t

R

-

t

A

) In accordance with VDI 2067, an appropriate

allowance for water heating per person is: 0,2 kW.

Example layout

For an example layout, a block of flats was

selected with 170 m² of living area and a heat

requirement of 100 W/m². A total of five persons

live in the house. The heat load amount is 17 kW.

Adding a drinking water allowance of 0.2 kW

results in a required heating capacity of 18 kW.

Depending on the power company, an additional

charge must then be made, to factor in disable

periods. The dimensioning and determination of

the bivalence point of the heat pump occurs graph-

ically in the inlet-temperature-specific heating

capacity diagram of the heat pump (in the example

55°C for a radiator heating system). Next, the heat

load for the standard outside temperature (the

lowest temperature of the year locally) and the

heat threshold are marked on the graph. In the

heating capacity diagram (Fig. 23) with the heating

capacity curve the outside-temperature-dependent

heat requirement is entered in simplified form as a

straight connecting line between the heat load and

start of heating. The point where the straight line

intersects with the nominal heating capacity curve

is measured on the x-axis and the temperature for

the bivalence point is read off there (in the

example this is approx. -4°C). The minimum

capacity of the second heat generator is the differ-

ence between heat load and the heat pump's max-

imum heating capacity on these days (in the

example the capacity required to cover the peak

load is approx. 6 kW).

23

Advertising
This manual is related to the following products: