REMKO WKF 120 Duo User Manual

Page 33

Advertising
background image

Minimum clearances of the outdoor units

1

2

3

4

5

6

>= 250

>= 1500

>= 1500

>= 250

>= 250

>= 300

>= 600

>= 600

>= 250

>= 1500

>= 2000

Fig. 33: Minimum clearances for installation of an outdoor unit in mm

1:

Next to a wall, air outlet open to the front, flow

restriction behind

2:

Next to a wall, air outlet toward the wall, flow

restriction to the front

3:

Between two walls, air outlet toward the wall,

open sides flow restriction front and rear

4:

In a niche, air outlet open to the front, flow

restriction behind and on both sides

5:

Next to a covered wall, air outlet open to the

front, flow restrictions behind and above

6:

Next to a covered wall, air outlet toward the

wall, flow restrictions behind and above

1

2

3

4

>= 1500

>= 300

>= 600

>= 600

>= 600

>= 250

>= 600

>= 600

>= 1500

>= 250

>= 1500

>= 3000

>= 600

>= 250

>= 3000

Fig. 34: Minimum clearances for installation of multiple outdoor units in mm

1:

Next to a wall, air outlet toward the wall, flow

restriction to the front

2:

In a niche, air outlet open to the front, flow

restriction behind and on both sides

3:

Between two walls, air outlet toward the wall

and to other units, open sides: flow restriction

front and rear

4:

Between two walls, air outlet toward the wall,

sides of outer units open: flow restriction front,

rear and on the sides of the inner units

33