13 troubleshooting and customer service, 1 troubleshooting and customer service, Troubleshooting and customer service – REMKO WKF 120 Duo User Manual

Page 47

Advertising
background image

13

Troubleshooting and customer service

13.1

Troubleshooting and customer service

The unit has been manufactured using state-of-the-art production methods and has been tested several

times to ensure that it works properly. However, in the event that malfunctions should occur, the unit should

be checked against the following list. Please inform your dealer if the unit is still not working correctly after all

of the functional checks have been performed.

Malfunction

Possible causes

Remedial measures

The heat pump does

not start or switches

itself off

Power failure, under-voltage

Check the voltage and, if necessary,

wait for it to come back on

Defective mains fuse / main switch

turned off

Exchange mains fuse, master switch on

Damaged power supply

Repair by specialist firm

Power company disable period

Wait until the power-company disable

period is over and the heat pump starts

up as required

Operational temperature limits too low

or too high

Observe temperature ranges

Setpoint temperature exceeded / incor-

rect mode

The set-point temperature has to be

higher than the heat generator temper-

ature, check mode

Disconnect the outdoor unit, then

establish the correct terminal sequence

using the connection plan Re-establish

voltage to the outdoor unit. Also make

sure that the earth conductor is con-

nected correctly.

Heating circuit pump

fails to switch off

Incorrect pump switching

Arrange to have pump switching

checked in the "Heating circuit" spe-

cialist level

Heat circuit pumps fail

to switch on

Incorrect mode set

Check mode

Control board fuse in indoor unit

switching cabinet faulty

Exchange the fuse on the left side of

the control board

Incorrect heating program set

Check heating program We recom-

mend the operating mode "heat" in the

cold heating season

Temperature overlapping, e.g. outside

temperature greater than room temper-

ature

Check temperature ranges. Probe test!

Red indicator light

Outdoor unit malfunction

Contact customer service