2 general mountig instructions, General mountig instructions – REMKO WKF 120 Duo User Manual

Page 29

Advertising
background image

The indoor and outdoor units must be connected to

refrigerant piping with dimensions (external diam-
eter)

3

/

8

" (=9.52 mm) and

5

/

8

" (=15.88 mm). At least

a two-wire control line must be routed between the

modules. Both the indoor and outdoor units require

a separate power supply.

WARNING!

All electric lines are in accordance VDE regula-

tions to dimension and to lay.

4.2

General mountig instructions

n

These instructions are to be observed when

installing the entire system.

n

The device should be delivered as near as

possible to the site of installation in its original

packaging in order to avoid transport damage.

n

The device is to be checked for visible signs of

transport damage. Possible defects must be

reported immediately to contract partners and

the forwarding agent.

n

Suitable sites for installation are to be selected

with regard to machinery noise and the set-up

process.

n

The shut-off valves for the refrigerant lines may

only be opened immediately before commis-

sioning of the system.

n

The exterior components are pre-filled with

refrigerant up to a distance of 10 meters from

the interior component. If the basic length of

the refrigerant line exceeds 10 metres, add

refrigerant.

n

Establish all electrical connections in accord-

ance with the relevant DIN and VDE standards.

n

The electrical power cables must be fastened

to the electrical terminals in the proper manner.

Otherwise there is a risk of fire.

n

See that neither refrigerant or pipes that carry

water pass through living- or sleeping areas.

NOTICE!

Open refrigerant pipes must be protected

against the introduction of moisture by means

of suitable caps or adhesive strips Refrigerant

pipes may not be kinked or compressed.

Refrigerant pipes may only be cut to length

with a suitable pipe cutter (use no hacksaws or

the like).

DANGER!

The installation of refrigerant equipment may

be undertaken only by trained specialist per-

sonnel!

DANGER!

All electrical installation work must be done by

an electrician.

29