8 connecting the refrigeration system, 1 connection of refrigerant lines, Remko wkf duo – REMKO WKF 120 Duo User Manual

Page 40: Connecting the refrigeration system

Advertising
background image

8

Connecting the

refrigeration system

8.1

Connection of refrigerant lines

n

The outdoor- and the indoor units are con-

nected with two copper pipes of refrigerator

quality having the dimensions 3/8" = 9,52 mm

and 5/8" = 15,88 mm (REMKO special acces-

sory).

n

Observe the permitted bending radius for the

refrigerant pipes during installation in order to

prevent kinks. Never bend a pipe twice in the

same place in order to prevent embrittlement

or crack formation.

n

Assure suitable fastening and insulation when

laying the refrigerant pipes.

n

The copper pipes are to be flared to make the

connections to the units. In doing so, check

that the flare has the correct shape and suit-

able union nuts. (Fig. 40 to Fig. 42).

2

1

Fig. 40: Deburring the refrigerant line

1: Refrigerant line

2: Deburrer

1

Fig. 41: Flanging the refrigerant line

1: Flanging tool

Fig. 42: Correct flange shape

Copper piping Out-

side diameterer

Flare dimensions ø A

3/8" = 9,52 mm

12.4 - 12.8 mm

5/8" = 15,88 mm

21.9 - 22.3 mm

REMKO WKF Duo

40

Advertising
This manual is related to the following products: