ID

Description

Details

8140

Upper application area

(heating)

The guaranteed application area of the external unit in heating mode is

currently exceeded

8141

Lower application area

(cooling)

The temperature has currently dropped below the guaranteed application

area of the external unit in cooling mode.

8142

Upper application area

(cooling)

The guaranteed application area of the external unit in cooling mode is

currently exceeded

8223

SD card error (host)

SD card error (host): The SD card is either not inserted correctly or an

error has occurred.

8224

SD card error

SD card error (CP): The SD card is not inserted or an error has occurred.

8225

CP dew point moni-

toring

Dew point monitoring was activated but no control panel (with integrated

humidity and temperature probe) was assigned to the cooling circuit to

calculate the dew point.

8226

Temp. dropped below

min. inlet temp.

Temp. dropped below min. inlet temp. (or dew point) - cooling request is

suppressed

8227

Hygiene function: Set-

point not reached

The hygiene function was cancelled due to the maximum runtime being

reached before attaining the set temperature.

8229

2nd heat generator

active

Due to the return temperature being too low during defrosting, the 2nd

heat generator was activated.

Error

ID

Description

Details

7050

Anti-freeze protection

The anti-freeze protection in the HP's heat exchanger was triggered due

to an inlet temperature of less than 5°C. After eliminating the cause of the

error, the controller must be restarted to reset the error.

7200

Open contact - storage

tank 1 bottom probe

S02

Open contact - storage tank 1 bottom probe

7201

Short circuit - storage

tank 1 bottom probe

S02

Short circuit - storage tank 1 bottom probe

7202

Open contact - storage

tank 1 middle probe

S09

Open contact - storage tank 1 middle probe

7203

Short circuit - storage

tank 1 middle probe

S09

Short circuit - storage tank 1 middle probe

7204

Open contact - storage

tank 1 top probe S08

Open contact - storage tank 1 top probe

7205

Short circuit - storage

tank 1 top probe S08

Short circuit - storage tank 1 top probe

7206

Open contact - external

probe S10

Open contact - external probe

7207

Short circuit - external

probe S10

Short circuit - external probe

51