The heat pump requires a constant, minimum

medium volume of approx. 10 litres per kW of

heating capacity to guarantee power for

defrosting and to assure a minimum running

time.

n

The stop cocks supplied are to be positioned

directly at the connections for the heat pump

inlet and return heating circuit. The shut-off

valves each contain a thermometer.

Fig. 38: Shut-off valves

Turning the thermometer heads serves to close

or open the stop valves! The dial be brought

into the desired position.

n

Install the dirt traps delivered with the unit out-

side the heat pump in the return flow. Ensure

that the dirt trap remains accessible for inspec-

tion.

n

Be sure to position one gate valve upstream

and another downstream of the dirt traps. This

ensures that the dirt traps can be checked at

any time without loosing water.

n

The dirt traps must be checked each time

maintenance is performed on the system.

n

Additionally, a hand-operated bleeder is

installed on the indoor unit for additional

bleeding of the heat pump.

n

All visible metallic surfaces must be addition-

ally insulated.

n

Cooling mode via the heating circuit requires a

completely vapour diffusion tight insulation

along the entire length of the pipework.

n

All outgoing heating circuits, including the con-

nections for water heating, are to be secured

against circulating water by means of check

valves.

n

Before being placed in service, the system

must be thoroughly flushed. Conduct a seal

test and perform a thorough bleeding of both

the indoor unit and the entire system according

to DIN standards - repeatedly, if necessary.

Actual schemas for hydraulic integration can

be found on the internet at www.remko.de