WAGO MCS DC power connector

-48VDC Power Supply (removed from back panel)

Input voltage: -48VDC

Min imum vo lta ge: -40 VDC
Maximum voltage: -60 VDC

Maximum operating current: 0.5A

The DC power source must be:

Electrically isolated from any AC source

Reliably connected to earth ground

Capable of providing up to 100 Watts of continuous power

D.2: Over-Current Protection

Over-current protection requirements:

10 Amp fast trip

Double pole

DC rated

Over-current protection devices (e.g., circuit breakers) must be provided as part of each
equipment rack and are not included with the Console Server. The device must be
located between the DC power source and the Console Server.

D.3: DC Supply Connector

The supply input connectors are provided with each Console Server; the conductors
are not.

Conductor specifications:

Material:

copper only

Wire gauge:

16 AWG

Insulation rating:

75 °C

minimum, low smoke-fume, flame retardant Branch

circuit cable.

Insulation color:

per applicable national electrical codes.

Grounding cable insulation color:

green/yellow