Connect Power to the Liqui-tect Panel

The Liqui-tect panel requires 24VAC for proper operation. Liebert recommends using the optional

Transformer Module manufactured by Liebert or another UL-approved Class 2 power unit to obtain

proper voltage. If the power unit is not a Class 2 circuit, it must be protected with an IEC 5 x 20mm

time lag 2A fuse. For information, consult your local dealer, Liebert representative or the Liebert

Worldwide Support Group.

2.4.1 Input Power Connections - Small Enclosure

To connect electrical power:
1. Run conduit and electrical wiring from building to the Liqui-tect panel.
2. Use copper wires only; proper wiring to use for 24VAC power is 18-22 AWG stranded and shielded

(18 AWG is recommended—see Table 4). Strip wires 1/2".

Figure 5

Electrical connections to panel

3. Secure the incoming electrical service wires to the Liqui-tect panel’s 24VAC input by sliding the

wires into TB1, the 24VAC input terminal block. There is no polarity requirement when

connecting to TB1. The ground wire must be connected to the earth ground terminal located on

the side of the panel (see Figure 5).

!

WARNING

Check that power is removed from wires prior to installation.

!

CAUTION

The Liqui-tect panel is designed for use on properly grounded (earthed) 24VAC power, 50Hz

or 60Hz. The ground wire for the power lead must be wired to the earth ground terminal (stud

located next to the 24VAC terminal block).
This equipment is intended to be installed by a qualified and certified electrician who must

review and approve customer supplied wiring and circuit breakers, verify correct input and

grounded (earthed) connections to ensure compliance with technical standards and national

and local electrical codes.

!

WARNING

Be sure that the power wiring is disconnected from the Liqui-tect panel before installing any

wiring to this unit.

SW3

EGND1

TVS3

TB1

FB2

R4

24V Power

Reset

24VAC input

connector

24VAC wiring

(red & white)

External wiring

through knockout

Earth ground

terminal

Ground wire