Figure 16 menu overview - system and control menu – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 28

Advertising
background image

System and Control Options

24

Figure 16 shows the main options available from the System & Control menu.

Figure 16 Menu overview - System and Control menu

Opening Screen

LIQUI-TECT PANEL

DD-MON-YY HR:MM:SS

VERSION X.X.X

PRESS

=STATUS/SETUP

Main Menu

VIEW STATUS

> SYSTEM AND CONTROL

↑↓

=NEXT

=SELECT

Login Screen

LOGIN

AAAA

↑↓

=SELECT

=NEXT/END

Setup System

> SETUP SYSTEM

RESET LATCHED ALARM
CLEAR ALARM HISTORY
CLEAR ZONE TREND

See

Section

6.2

SETUP ZN1 ZONE 1
SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS
SETUP REALARM DELAY
SETUP MAPMODE
SETUP SYSTEM INFO

Reset Latched Alarm

SETUP SYSTEM

> RESET LATCHED ALARM

CLEAR ALARM HISTORY
CLEAR ZONE TREND

See

Section

6.9

Reset Latched Alarms

RESET LEAK & FAULT
LATCHED ALARMS? Y

↑↓

=Y/N

=END

System & Control options

Clear Zone Trend

SETUP SYSTEM
RESET LATCHED ALARM
CLEAR ALARM HISTORY

> CLEAR ZONE TREND

See

Section

6.11

Clear Zone Trend

CLEAR ZONE TREND
ARE YOU SURE? Y

↑↓

=Y/N

=END

Clear Alarm History

SETUP SYSTEM
RESET LATCHED ALARM

> CLEAR ALARM HISTORY

CLEAR ZONE TREND

See

Section

6.10

Clear Alarm History

CLEAR ALARM HISTORY
ARE YOU SURE? Y

↑↓

=Y/N

=END

Setup Zone 1 Menu

SETUP ZN1 ZONE 1
CONNECTED: N
LABEL: ZONE 1
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA

See

Section

6.3

Setup Mapmode

SELECT ZONE TO MAP

> ZN1 ZONE 1

ZN2 ZONE 2
VIEW LAST MAP

See

Section

6.7

Mapping Options

MAPPING ZN1 ZONE 1
CURRENT:

0UA

DISTANCE:

----

ENTRIES:0

ESC=EXIT

Setup System options

Setup System Info

SETUP SYSTEM INFO

CHANGE PASSWORD
CHANGE DATE & TIME
FACTORY DEFAULTS

See

Section

6.8

Setup Zone 2 Menu

SETUP ZN2 ZONE 2
CONNECTED: N
LABEL: ZONE 2
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA

See

Section

6.4

Setup Alarm Outputs

SELECT LONGEST
CABLE CONNECTED

> 0-500FT (0-152.4 M)

0-1000FT (0-304.8M)
0-1500FT (0-472.2M)
0-2000FT (0-609.6M)
0-2500FT (0-762.0M)
0-3000FT (0-914.4M)
0-4000FT(0-1219.2M)
0-5000FT(0-1524.0M)

See

Section

6.5

Normally Open / Closed

ARE LEAK & FAULT
RELAYS NORMAL OPEN
OR NORMAL CLOSED? NO

↑↓

=NO/NC

=END

Latched / Unlatched

IS LEAK & FAULT
ALARM LATCHED? Y

↑↓

=Y/N

=END

Change Password

Change Date & Time

Factory Defaults

CHANGE PASSWORD

AAAA

See

Section

6.8.1

CHANGE DATE & TIME

DAYLIGHT SVG TIME: Y

18-MAY-02 10:56:30

See

Section

6.8.2

RESTORE ALL DEFAULTS
ARE YOU SURE? N

See

Section

6.8.3

Change Realarm Delay

CHANGE REALARM DELAY

5 MINUTES

↑↓

=SELECT

=END

See

Section

6.6

Setup System Info options