7 setup system - setup mapmode, Table 11 default mapping values, Setup system - setup mapmode – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 37: Table 11, Default mapping values

Advertising
background image

System and Control Options

33

6.7

Setup System - Setup Mapmode

Mapping involves measuring the exact location of various points along the leak detection cable. This

greatly simplifies the use of the Liqui-tect Monitoring System to quickly pinpoint the location of a leak.

The Liqui-tect Monitoring System determines the location of a leak by computing its distance along the

leak detection cable. By setting off alarms with a damp paper towel or sponge and marking each reading

on a map of the floor, you can define various points along the cable for later reference in finding a leak.

Up to 254 points can be mapped.

After the leak detection cable has been laid and properly connected, as described in 3.1 - Connecting

Leak Detection Cable Inputs, follow these steps to map the system:
1. Draw a floor plan that shows the routing of the leak detection cable, including any jumpers used

(non-sensing cable).

2. Using the LCD on the front panel of the Liqui-tect Monitoring System:

Log In and Choose Setup System
a. From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 6.1 - Login for help)

.

b. Enter your password at the Login screen.
c. From the System and Control Menu, use the arrows

↑↓

to

choose Setup System, then press Enter

.

Select Setup Mapmode
d. From the Setup System Menu, shown at right, use the

arrows

↑↓

to

choose Setup Mapmode and press Enter

.

e. Use the following instructions to set up the mapping of each zone.

Set Up Mapping for Zone 1 or Zone 2
f. Use the arrows

↑↓

to

choose a zone—either ZN1 Zone 1 or

ZN2 Zone 2—from the Select Zone to Map Menu, and press

Enter

.

The Liqui-tect Monitoring System is now ready for you to short the

cable, as described in steps 3 through 6.

3. Select the first point to be mapped and mark it on the floor map as

point “X” (where X represents 1 for the first point, 2 for the second,

and so on, up to 254). Determine the exact location of the point by

measuring the distance from the panel to the point or otherwise

describing its location (for example, “at front of chiller”).

4. Wrap a damp paper towel or sponge around the selected point on

the cable to cause a short in the cable and trigger an alarm.

5. After about 30 seconds, the Liqui-tect panel annunciates a short beep. The LCD displays the

computed distance to the leak.

6. Remove the paper towel and dry the cable. In approximately 20 seconds, the Liqui-tect panel

annunciates a long beep indicating the short has been removed.

7. Go to the next point and repeat this process (steps 3 through 6) until the entire cable has been

mapped. Up to 254 points can be mapped.

When complete, press the ESC key on the LCD to exit mapping mode and return to the previous screen.
Table 11 shows the default mapping settings for each zone.

NOTE
You must perform the automatic calibration steps in 6.3.4 - Auto Calibration before mapping

can commence. The leak detection cable is 12 in. (30.48cm) to 18 in. (45.72cm) longer than the

nominal length, which allows a service loop should the cable need to be replaced. Automatic

calibration enables the Liqui-tect system to determine the cable’s exact length.

Table 11

Default mapping values

Option

Default setting

Current

0UA, where UA represents µA or microAmps

Distance

(none)

Setup System Menu

SETUP ZN1 ZONE 1
SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS

↑↓

=NEXT

=SELECT

SETUP REALARM DELAY

> SETUP MAPMODE

SETUP SYSTEM INFO

Select Zone to Map

SELECT ZONE TO MAP

> ZN1 ZONE 1

ZN2 ZONE 2

↑↓

=NEXT

=SELECT

VIEW LAST MAP

Mapping Options

MAPPING ZN1 ZONE 1
CURRENT:

0UA

DISTANCE:

----

ENTRIES:0

ESC=EXIT