3 typical sequence, Typical sequence, Figure 3 – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 7

Advertising
background image

Introduction

3

1.3

Typical Sequence

Figure 3 shows a typical sequence of how the Liqui-tect Monitoring System functions after detecting

a leak, contamination or cable break in either Zone 1 or Zone 2. Responses depend on configuration

settings. This example shows what happens when a leak is detected.

Figure 3

Example of typical sequence: Analog input reaches high setpoint

LIQUI-TECT PANEL
05-SEP-02 14:04:13

V5.100.0

PRESS =STATUS/SETUP

ESC

ESC

Entry in Alarm History Log

(if alarms defined as Latched)

ZONE 1
LEAK @ 3495ft

29-AUG-03

09:29:10

Entry in Alarm History Log

The alarm is cleared

(automatically if Unlatched; must be

cleared manually if Latched)

The LCD stops flashing

RETURN TO NORMAL

The leak is controlled.

The horn sounds (audible horn on

the controller board—silence horn by

pressing any key on the LCD keypad)

The LCD flashes

ALARM CONDITION DETECTED

A leak is sensed along the cable

defining Zone 1.

RESPONSES TO AN ALARM

RETURN-TO-NORMAL SEQUENCE

Entry in Zone Trend Log

(if alarms defined as Unlatched)

The horn stops sounding

(if user hasn’t silenced it)

ZONE 1
ALARM RESET - LCD

29-AUG-03

09:42:11

ZONE 1
NO LEAK

29-AUG-03

09:42:11

LIQUI-TECT PANEL
05-SEP-02 14:04:13

V5.100.0

PRESS =STATUS/SETUP

ESC

ESC

Advertising