0 specifications, 1 liquitect panel specifications, Pecifications – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 44: Liqui-tect panel specifications, 1 liqui-tect panel specifications

Advertising
background image

Specifications

40

7.0

S

PECIFICATIONS

7.1

Liqui-tect Panel Specifications

Power

Requirements

Small Enclosure

Large Enclosure

NOTE

LPS0240

115VAC

LPL1150

230VAC

LPL2300

If the equipment is

used in a manner

not specified by the

manufacturer, the

protection provided

by the equipment

may be impaired.

24VAC

±

10%

of nominal;

50/60 Hz, 0.3A,

8VA

115VAC ±10%

of nominal;

60 Hz, 4A,

460VA

230VAC ±10%

of nominal;

50 Hz, 0.5A,

115VA

Dimensions

W x D x H, in. (mm)

14-1/4 x 2-3/4 x 12

(361.95 x 69.85 x 304.8)

18 x 2-3/4 x 18

(457.2 x 69.85 x 457.2)

Weight (Assembled)

7.68 lb. (3.48 kg)

20.56 lb. (9.33 kg)

Enclosure Type

NEMA 1

Liquid Crystal Display (LCD)

Four line, 20 character, backlit

Mounting Surface

Building Wall or Structural Member

Ambient Operating

Environment

32°F to 104°F (0°C to 40°C)

0% RH to 95% RH (non-condensing)

Processor Specifics

Model

MC68HC16Z1

Clock speed

20MHz

Total RAM

128Kb

Total FLASH

256Kb

Total NVRam

32Kb

A/D Resolution (Analog IN)

14 bits

Clock Type

Real-Time Clock

Clock battery backup type

Internal

Clock battery life

10 years, constant, no power

Communications

SiteScan Web

IGM Protocol, 422

Agency Listings

No Transformer Module

With Transformer Module

UL

UL3121

UL3121,

UL1012

UL3121,

UL1585

CSA

C22.2 No. 1010

C22.2 No. 1010,

C22.2 No. 66

C22.2 No. 1010,

C22.2 No. 107.1

CE

Yes

Yes

FCC Compliance

CFR 47 Part 15

Inputs & Outputs (Quantity)

Cable Input (2)

N/A

Analog Output (2)

4-20mA signal output

Alarm Output (4)

24VAC, 1A

Advertising