Connections and Configuration

13

3.1

Connecting Leak Detection Cable Inputs

The leak detection cable inputs are found on the lower right side of the Liqui-tect panel’s printed wir-

ing assembly board. There are two terminal blocks for the inputs; the lower terminal block is for the

Zone 1 cable and the terminal block above it is for a second leak detection cable, Zone 2.
To determine the proper wire size, see Table 4 - Wiring specifications.

3.1.1 Attaching Leak Detection Connection Cable to the Panel

To attach a leak detection connection cable:
1. Disconnect electrical power to the Liqui-tect

panel.

2. Locate the Zone 1 and Zone 2 cable connectors

on the controller board. They can be found on

the lower right corner of the board (see 1.4 -

Controller Board Overview). The Zone 1

connector is Cable 1 or TB9. The Zone 2

connector (Cable 2 or TB6) is just above it.

3. If necessary, remove a conduit knockout to

permit wire entry into the Liqui-tect panel

enclosure.

4. Bring the white connection cable

(CONNECT10) into the Liqui-tect panel

enclosure through a conduit knockout or

access slot.

5. Loosen a screw on the terminal block and slip

the stripped end of the appropriate wire into

the terminal block according to the color-coded

wiring key (see illustration at right).
Note that the WHITE wire connects to the “Y

slot. The red wire connects to the “R” slot, the

green wire connects to the “G” slot and the black wire to the “B” slot.

6. Tighten the screw until it holds the wire snugly.
7. Repeat for each of the four wire strands in the connection cable.

NOTE
Each terminal block is a removable, two-part assembly to permit easier connection of more

than one input at a time. If making multiple connections, grasp the upper portion of a block

and pull firmly to the right until the assembly pulls apart.
After making the connections, push the removed piece back into the portion attached to the

printed wiring assembly until the terminal block pieces lock together.

TB9

Cable 1

Y

B

G

R

Y

B

G

R

TB6

X6

Leak Detection Cable

Terminal Blocks:
Zone 2
Zone 1

WIRING

CONNECTIONS

Black Wire

Red Wire
Green Wire

WHITE Wire