4 rs422 sitescan web connector, 5 disable the audible horn, Rs422 sitescan web connector – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 21: Disable the audible horn

Advertising
background image

Connections and Configuration

17

3.4

RS422 SiteScan Web Connector

The Liqui-tect panel will interface with Liebert’s SiteScan Web enterprise

monitoring system. SiteScan can be used to monitor the Liqui-tect panel from

a host computer and silence the audible alarm. The terminal block connector,

TB8, is on the bottom edge of the board, near the left corner.
To connect the SiteScan Web to the Liqui-tect panel:
1. Disconnect electrical power to the Liqui-tect panel.
2. If necessary, remove a conduit knockout to permit wire entry into the

Liqui-tect panel enclosure.

3. Bring the wire(s) into the Liqui-tect panel enclosure through a conduit

knockout or access slot.

4. Loosen the appropriate screw and slip the stripped end of the wire into the

terminal block. Note that the wires are polarity sensitive.

5. Tighten the screw until it holds the wire snugly.

3.5

Disable the Audible Horn

The panel’s audible horn is enabled by default. You may disable it as follows:
1. Set DIP switch 1, the first switch, to the ON position (up) to disable the audible horn.
2. Press the reset button to initiate the change.

To re-enable the horn, set DIP switch 1, the first switch, to the OFF position (down) and press the

reset button.

A

B

RS422 SiteScan

Web connector

R16

R17

R18

DS3

DS4

K1

K2

K4

A

1

SW2

SW1

R4

O N

2

3

4

5

6

7

8

1

O N

2

R1

DS1

Pwr On

24V Pow

3

4

5

6

7

8

DIP switch 1

Audible horn

Reset

switch

Advertising