4 setup system - setup zn2 zone 2, Setup system - setup zn2 zone 2 – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 33

Advertising
background image

System and Control Options

29

6.4

Setup System - Setup ZN2 Zone 2

The Liqui-tect panel has two independent zones—ZN1 and ZN2—that

may be configured individually. Each zone can monitor up to 5,000 ft.

(1524m) of leak detection cable.
To configure the second zone:

• In the Setup System Menu, choose Setup ZN2 Zone 2 (see above

right).

• Follow the same procedures used in setting up Zone 1, as

described in the previous section, 6.3 - Setup System - Setup

ZN1 Zone 1.

NOTE
The setup options are identical for both zones, except the

name of the zone differs.

Setup System Menu

SETUP ZN1 ZONE 1

> SETUP ZN2 ZONE 2

SETUP ALARM OUTPUTS

↑↓

=NEXT

=SELECT

SETUP REALARM DELAY
SETUP MAPMODE
SETUP SYSTEM INFO

Setup Zone 2 Menu

SETUP ZN2 ZONE 2

> CONNECTED: N

LABEL: ZONE 2

↑↓

=NEXT

=SELECT

UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA