4 auto calibration, 5 set up sensitivity for water detection, Auto calibration – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 31: Set up sensitivity for water detection

Advertising
background image

System and Control Options

27

6.3.4

Auto Calibration
The auto calibration feature is designed to allow compensation for the

resistance tolerances in the two legs of the sensing wires.
As soon as cable is connected, the panel begins calculating the cable

length. Initiating the auto calibration feature allows the user to mod-

ify the distance to account for any discrepancies. Once the new dis-

tance is entered, the panel adjusts for the required offset between the

calculated value and the user value.
To initiate automatic calibration for ZN1:

• From the Setup Zone 1 Menu, choose Auto Calibrate, as shown

at right, and press Enter

.

• At the Change Maximum Length screen, you may change the

maximum length of cable protecting this zone:

• To begin calibration without changing this value, press

Enter

.

• To change the value, press and hold one of the arrow keys

↑↓

to scroll through the numbers, then press Enter

.

• The next screen displays the progress of calibration.

6.3.5 Set Up Sensitivity for Water Detection

Each zone may be set up with a sensitivity level at which water is

detected.

• The most sensitive setting is 25 µA—minimal water is required to

trigger an alarm.

• The least sensitive setting is 300 µA. At this setting, the cable will

be submerged in water for a longer period before an alarm is trig-

gered.

To change the setting:

• From the Setup Zone 1 Menu, choose Water Detect, as shown at

right, and press Enter

.

• The Water Detection Sensitivity screen displays the value for

detection of water (in the example at right,

150 UA

, where UA rep-

resents µA or microAmps):

• To change the value, press and hold one of the arrow keys

↑↓

to scroll through the numbers 25-300.

• Press Enter

.

Setup Zone 1 Menu

SETUP ZN1 ZONE 1
CONNECTED: Y
LABEL: ZONE 1

↑↓

=NEXT

=SELECT

UNITS: FT

> AUTO CALIBRATE

WATER DETECT:150 UA
CONTAMINATED:050 UA

Change Maximum Length

CHANGE MAX LENGTH

1000 FT

↑↓

=SELECT

=ACCEPT

Auto Calibration Progress

THIS SCREEN WILL SHOW
AUTO CALIBRATION
TAKING PLACE

Setup Zone 1 Menu

SETUP ZN1 ZONE 1
CONNECTED: Y
LABEL: ZONE 1

↑↓

=NEXT

=SELECT

UNITS: FT
AUTO CALIBRATE

> WATER DETECT:150 UA

CONTAMINATED:050 UA

Water Detection

Sensitivity

CHANGE SENSITIVITY

FOR WATER DETECT

150 UA

↑↓

=SELECT

=END