Connections and Configuration

12

3.0

C

ONNECTIONS

AND

C

ONFIGURATION

Input and output connections to the Liqui-tect panel may be made in any order—it is not necessary,

for example, to make all input connections before making any output connections. Use copper conduc-

tors only for all wiring.

!

CAUTION

Be sure that the power wiring is disconnected from the Liqui-tect panel before installing any

wiring to this unit or changing input or output connections.

Table 4

Wiring specifications

Connection

Supported Wire Type

Maximum Wire Length

Rating

Cable

Input

4 wire Liebert Connection Cable

(CONNECT10) - furnished with

Liqui-tect panel

Connection cable - 10 ft. (3m)

Leak detection cable - 5000 ft. (1524m)

N/A

Alarm

Output

18-22 AWG Stranded & Unshielded

18 AWG* (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

18 AWG*

@ 1A 200 ft. (60m)

24VAC @ 1A

20 AWG

@ 1A 100 ft. (30m)

22 AWG

@ 1A 75 ft. (23m)

Analog

Output

18-22 AWG Stranded & Unshielded

18 AWG* (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

750 ft. (225m)

4-20mA

Signal

Output

Communication

RS232

Null Modem Cable

50 ft. (15m)

N/A

Communication

IGM422

SiteScan

18-22 AWG Stranded & Shielded

22 AWG* (recommended)

Non Plenum - Belden 9461

Plenum - Belden 88761

1000 ft. (300m)

N/A

24VAC Power

Connection

(TB7)

18-22 AWG Stranded & Unshielded

18 AWG* (recommended)

Non Plenum - Belden 8770

Plenum - Belden 88770

150 ft. (45m)

24VAC @ 1A

* Recommended