8 setup system - setup system info, 1 change password, Change the password – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 39: Reset password to the factory default (“aaaa”), Setup system - setup system info, Change password, 1 - change, Password .), Section 6.8 )

Advertising
background image

System and Control Options

35

6.8

Setup System - Setup System Info

The Setup System Info options allow users to:

Change Password—used for access to system setup functions
Change Date & Time/Automatic Daylight Saving Time—used to set the Liqui-tect panel’s

date and time and to enable automatic time change for Daylight Saving Time

Restore Defaults—returns the Liqui-tect panel to its factory settings

To change any Setup System Info features:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 6.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select Setup System

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup System Info and press Enter

.

• Use the following steps to access any of the Setup System Info options.

6.8.1 Change Password

A password is required to access the Liqui-tect panel’s system and

control options, as described in 6.1 - Login. The password consists of

four characters (see Table 7 for valid characters). The default pass-

word is AAAA.
Changing the password to “0000” eliminates the login requirement

and prevents the login screen from appearing.

Change the Password

To change the password:

• From the Setup System Info Menu, use the arrows

↑↓

to

choose

Change Password, then press Enter

.

• To change your password:

• Use the arrows

↑↓

to

choose a character.

• Press Enter

to advance to the next character position.

• When finished, press Enter

again.

Reset Password to the Factory Default (“AAAA”)

To reset the password to the factory default of AAAA:

• Locate DIP switch 1 on the unit’s circuit board (see 1.4 - Controller Board Overview) and move

switches 2, 7 and 8 to the OFF position (down).

• Move the second switch to the ON position, then to the OFF position.
• Move the seventh switch to the ON position, then to the OFF position.
• Move the eighth switch to the ON position, then to the OFF position.

The password should now be AAAA.

Setup System Menu

SETUP ZN1 ZONE 1
SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS

↑↓

=NEXT

=SELECT

SETUP REALARM DELAY
SETUP MAPMODE

> SETUP SYSTEM INFO

Setup System Info Menu

SETUP SYSTEM INFO

> CHANGE PASSWORD

CHANGE DATE & TIME

↑↓

=NEXT

=SELECT

FACTORY DEFAULTS

Change Password

CHANGE PASSWORD

AAAA

↑↓

=SELECT

=NEXT/END

Advertising