5 setup system - setup alarm outputs, Table 9 default settings - alarm outputs, Setup system - setup alarm outputs – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 34: Table 9, Default settings - alarm outputs

Advertising
background image

System and Control Options

30

6.5

Setup System - Setup Alarm Outputs

The Liqui-tect panel has six alarm outputs—three types for each zone:

• Digital alarm output for cable break detection - a change in state indicates a broken cable or con-

tamination on the cable

• Digital alarm output for leak detection - a change in state indicates a leak on the cable
• Analog alarm output for 4-20mA - the signal may indicate normal operation, the location of a

leak, a cable break or contamination

These outputs may have a wide variety of Liebert or other manufacturers’ equipment connected to

receive alarm notification.
To configure all alarm outputs:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 6.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select Setup Alarm Outputs

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup Alarm Outputs and press Enter

.

Table 9 shows alarm output features and their default settings: you

may specify the maximum cable length of analog alarm outputs, define

digital alarm output relays as Normally Open or Closed, and set up

alarms as Latched or Unlatched.
To change the default settings, use the steps following Table 9.
Table 9

Default settings - alarm outputs

Feature

Default

Other Options

LONGEST CABLE LENGTH

0-1000 ft. (0-304.8m) Up to 5000 ft. (1524m)

LEAK & FAULT RELAYS:

NORMALLY OPEN/CLOSED NO (Normally Open)

NC (Normally Closed)

LEAK & FAULT ALARM:

LATCHED/UNLATCHED

Y (Latched)

N (Unlatched)

Setup System Menu

SETUP ZN1 ZONE 1
SETUP ZN2 ZONE 2

> SETUP ALARM OUTPUTS

↑↓

=NEXT

=SELECT

SETUP REALARM DELAY
SETUP MAPMODE
SETUP SYSTEM INFO

Maximum Cable Length

SELECT LONGEST
CABLE CONNECTED

> 0-500FT (0-152.4 M)

↑↓

=NEXT

=SELECT

0-1000FT (0-304.8M)
0-1500FT (0-472.2M)
0-2000FT (0-609.6M)
0-2500FT (0-762.0M)
0-3000FT (0-914.4M)
0-4000FT(0-1219.2M)
0-5000FT(0-1524.0M)

Normally Open / Closed

ARE LEAK & FAULT
RELAYS NORMAL OPEN
OR NORMAL CLOSED? NO

↑↓

=NO/NC

=END

Latched / Unlatched

IS LEAK & FAULT
ALARM LATCHED? Y

↑↓

=Y/N

=END