Overview of Menus

18

4.0

O

VERVIEW

OF

M

ENUS

The Liqui-tect panel displays the Opening Screen at startup, as shown in Figure 14.
If any alarms are active, the Current Alarm screen appears. (Pressing any key on the LCD keypad

will silence the audible alarm.)
If no alarms are present, the LCD screen will alternately display the Opening Screen and a screen

showing NO ALARMS PRESENT.
If no alarms are present and the Enter

(Return) key is pressed, the Main Menu appears and pre-

sents two choices that lead to all functions within the panel:

• View Status (see 5.0 - View Status Options for step-by-step instructions)
• System and Control (see 6.0 - System and Control Options for detailed instructions)

4.1

View Status Overview

The View Status features are available to all users—no password is required. This permits all person-

nel to check on the status of any equipment or location being monitored. From this menu, any user

may:

• View cable status, the monitored cable length and the amount of current present (both zones)
• View data stored in the Alarm History Log
• View data stored in the Zone Trend Log

4.2

System and Control Overview

The System and Control options require a password. Authorized users may:

• Configure the Liqui-tect panel
• Reset any latched alarms
• Delete all records from the Alarm History Log
• Delete all records from the Zone Trend Log

Figure 14 Menu overview

Opening Screen

LIQUI-TECT PANEL

DD-MON-YY HR:MM:SS

VERSION X.X.X

PRESS

=STATUS/SETUP

(If any alarm is detected,

it appears automatically)

Main Menu

VIEW STATUS
SYSTEM AND CONTROL

↑↓

=NEXT

=SELECT

“View Status” selected

See Section

“System & Control” selected

See Section

> VIEW STATUS

SYSTEM AND CONTROL

↑↓

=NEXT

=SELECT

5.0

VIEW STATUS

> SYSTEM AND CONTROL

↑↓

=NEXT

=SELECT

6.0

View Status Menu

(All users - no password)

See Section

System & Control Menu

(Password required)

See Section

VIEW CABLE STATUS

VIEW ALARM HISTORY

VIEW ZONE TREND

5.1
5.2
5.3

SETUP SYSTEM

RESET LATCHED ALARM

CLEAR ALARM HISTORY

CLEAR ZONE TREND

6.2
6.9

6.10
6.11