System and Control Options

25

6.2

Setup System - Overview

The Setup System screen displays six options that allow you to configure zones with cable, alarm

outputs, the re-alarm delay time, log points to create a map and system details, such as changing the

login password or the system date and time:

• Setup ZN1 Zone 1
• Setup ZN2 Zone 2
• Setup Alarm Outputs
• Setup Re-Alarm Delay
• Setup Mapmode
• Setup System Info

6.3

Setup System - Setup ZN1 Zone 1

The Liqui-tect panel has two independent zones—ZN1 and ZN2—that

may be configured individually. Each zone can monitor up to 5,000 ft.

(1524m) of cable.
If neither zone is configured as connected, the screen displays the

message:

WARNING! NO ZONES ARE INSTALLED

To configure the first zone:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 6.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select Zone 1 to Configure

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup ZN1 Zone 1

and press Enter

.

• Use the steps following Table 8 to change the default settings for Zone 1.

Table 8 shows the features you may change for Zone 1, along with the default settings. By default,

Zone 1 is not connected.
To activate Zone 1, you must specify it as connected. Other features that may be altered include the

name of the zone, the measurement units, and the sensitivity for detection of water and of contamina-

tion. You may also initiate automatic calibration, during which the Liqui-tect panel determines the

length of cable and parameters.
Table 8

Default settings - Zone 1

Feature

Default

Other Options

CONNECTED

N (Not connected)

Y (Connected)

LABEL

ZONE 1

Any name (up to eight characters)

UNITS

FT (feet)

M (meters)

AUTO CALIBRATE

Automatically calculates cable length

Allows adjustment to calculated length of cable

SENSITIVITY FOR

WATER DETECT

150 UA

Can define between 25µA and 300µA

SENSITIVITY FOR

CONTAMINATED

50 UA

Can define between 20µA and 300µA

Setup System Menu

> SETUP ZN1 ZONE 1

SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS

↑↓

=NEXT

=SELECT

SETUP REALARM DELAY
SETUP MAPMODE
SETUP SYSTEM INFO

Setup Zone 1 Menu

SETUP ZN1 ZONE 1

> CONNECTED: N

LABEL: ZONE 1

↑↓

=NEXT

=SELECT

UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA