Installing the inverter

Page 16

Operating Instructions Powador 12.0 TL3-20.0 TL3

Authorised electrician

NOTE

Remove only the connection cover (blue). Opening the housing cover (grey) will invalidate

the warranty.

7.2

Making the electrical connection

Make the connection to the PV generator via the plug connectors and the grid connection via the PCB terminals in

the connection area of the inverter. Note the following conductor cross-sections:

AC connection

DC connection

Max. conductor cross-section without wire sleeves

16 mm²

Dependent on the plug that

is used

Max. conductor cross-section with wire sleeves

10 mm²

Length of insulation to be stripped off

10 mm

3

2

1

5

4

Figure 6: Connection area: electrical connection

Key

1

DC isolator switch

3

AC connection terminals

2

8 (2 x 4) MC4-compatible DC plug connector for

PV generator

4

Cable fitting (M40) for AC connection

5

Cable fittings (M16) for housing ground connection

Advertising