Configuration and Operation

Operating Instructions Powador 12.0 TL3-20.0 TL3

Page 37

Country-

spec. Setting

Menu

level

Display/settings

Action in this menu/meaning

0

1

2

3

0

“Parameters” menu

"

Press the right arrow button or the OK button.

NOTE: The inverter does not display the “Parameters”

menu in the standard configuration. To display the

Parameters menu:
1. Open the menu.
2. Simultaneously hold down the up and down

buttons for several seconds.

0

1

2

3

1

Country

1. Enter the four-digit password using the 4-way

button. The password is unit-specific.

2. Confirm the entry with the OK button.
3. Set the desired country setting.
NOTE: This option influences the country-specific

operating settings of the inverter. Please consult

KACO service for further information.

0

1

2

3

1

Grid type/

guideline

"

Select the grid type for the inverter’s installation

location.

AU, BG, FR,

GR, PT, ES,

CZ, KR

0

1

2

3

1

Switch-off volt.

The inverter is equipped with redundant 3-phase

monitoring. If the grid frequency exceeds or drops

below the configured values, the inverter switches off.

The minimum switch-off threshold can be set in 1 V

increments.

"

Configure the switch-off values for undervoltage

and overvoltage.

"

Where necessary, set period from occurrence of

the fault to shutdown of the inverter.

DE, AU, BG,

FR, GR, HU,

IL, PT, ES, CZ,

KR

0

1

2

3

1

Switch-off freq.

The inverter monitors the grid frequency continuously.

If the grid frequency exceeds or drops below the

configured values, the inverter switches off.

"

Set limit values for underfrequency and

overfrequency in 0.1 Hz increments.

"

Set period from occurrence of the fault to shutdown

of the inverter.

DE, BE, FR, IT,

AT, PL, UD

0

1

2

3

1

Overvoltage shutd.

"

Specify the shutdown threshold for fast and slow

overvoltage shutdown.

"

Set period from occurrence of the fault to shutdown

of the inverter.

DE, FR, GB,

HU, IL, IN, IT,

AT, PL, RU, ES,

TH, ZA, UD

"

Activate or deactivate password protection.

"

Specify the shutdown threshold for overvoltage

shutdown.

The 10-minute average for the measured voltage as

per EN50160 is used.

"

Set period from occurrence of the fault to shutdown

of the inverter.

BG, CZ, FR

0

1

2

3

1

Voltage drop

The voltage drop between the inverter and the feed-in

meter is added to the limit value that was set for grid

shutdown according to EN 50160. The limit value can be

set from 0 to 11 V in 1 V increments.

"

Specify the switch-off value for the voltage drop

(0 to 11 V).