Maintenance/Troubleshooting

Page 50

Operating Instructions Powador 12.0 TL3-20.0 TL3

Status

Display

Explanation

Action

FS 48

Line failure:

underfreq.

Grid frequency is too low.

This fault may be grid-related.

"

Notify your

authorised

electrician.

E

FS 49

Line failure:

overfreq.

Grid frequency is too high.

This fault may be grid-related.

"

Notify your

authorised

electrician.

E

FS 50

Line failure: average

voltage

The grid voltage measurement

according to EN 50160 has exceeded

the maximum permitted limit value.

This fault may be grid-related.

"

Notify your

authorised

electrician.

E

FS 57

Waiting for

reactivation

Waiting time of the inverter after

a fault.

Inverter does not switch on

again until the country-specific

time has elapsed.

FS 58

Control board

overtemp.

The temperature inside the unit was

too high. The inverter switches off to

prevent damage to the hardware.

"

Provide for sufficient

ventilation.

E

FS 59

Self test error

A fault occurred during a self-test.

"

Notify your

authorised

electrician.

E

OS 60

Generator voltage

too high

The inverter does not begin feeding

into the grid until the PV voltage falls

below a specified value.

-

-

OS 61

External limit (%)

The external limit Power control was activated by the grid operator.

The inverter limits its power.

OS 63

Measured values

P(f)/frequency-dependent power reduction: Frequency-dependent

power reduction will be activated when the BDEW (German Association

of Energy and Water Industries) Medium Voltage Directive goes

into effect. Power reduction starts at a frequency of 50.2 Hz.

OS 64

Measured values

Output current limiting: The AC current is limited once the specified

maximum value has been reached.

FS 67

Fault at power

section 1

There is a fault in the power section.

"

Notify your

authorised

electrician.

E

FS 70

Fan error

The fan is malfunctioning.

"

Replace

defective fan.

E

FS 73

Standalone grid err.

Standalone mode was detected.

-

-

OS 74

External idle power

requirement

The grid operator limits the feed-in

power of the inverter.

-

-

OS 79

Insulation

measurement

PV generator’s insulation is being

measured

-

-

FS 80

Insulation meas.

not possible

The insulation measurement cannot

be performed because the generator

voltage is too volatile.

-

-

FS 81,

82,

83

Protection

shutdown line volt.

L1 L2, L3

Overvoltage has been detected on

a conductor. An internal protective

mechanism has disconnected the

device to protect it against damage.

"

In case of repeated

occurrence:

Notify your

authorised

electrician.

E

Table 3:

Operating status and fault messages on the display