Maintenance/Troubleshooting

Page 48

Operating Instructions Powador 12.0 TL3-20.0 TL3

9.5

Messages on the display and the “Fault” LED

Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The triggering levels are

defined in standards, e.g. VDE0126-1-1. The inverter shuts down if the values exceed or fall below the approved levels.

9.5.1 Display of status and fault messages

Display

Fault LED (red)

FS (fault status)

ON

Fault signal relay has switched.

Feed-in was ended due to a fault.

OS (operating status)

OFF

The fault signal relay releases again.

The inverter feeds back into the grid again after

a country-specific time period.

Details regarding the fault or operating status can be found either on the display or in the data that was recorded

through the RS485 interface.

Status and fault signals

The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs.

BS = operating status, FS = fault status;
B = Action of the operator
E = The indicated work may only be carried out by an authorised electrician.
K = The indicated work may only be carried out by a service employee of KACO new energy GmbH.

Status

Display

Explanation

Action

OS 1

Waiting for feed-in

Self-test: The grid parameters and

generator voltage are being checked.

-

-

OS 2

Generator voltage

too low

Insufficient generator voltage and

power,

status before the transition to night

shutdown

-

-

OS 8

Self-test

Checks the shutdown of the power

electronics as well as the grid relay

before feed-in mode.

-

-

FS 10

Temperature in

unit too high

In case of overheating, the inverter

switches off. Possible causes:

Ambient temperature too high.

Fans covered.

Inverter defective.

"

Cool off the area

around the inverter.

"

Uncover the fans.

"

Notify your

authorised

electrician.

B

B

E

OS 11

Measured values

Power limitation: If the generator power is too high, the inverter limits

itself to the maximum power (e.g. around noon if the generator capacity

is too large).

Table 3:

Operating status and fault messages on the display