Installing the inverter

Page 18

Operating Instructions Powador 12.0 TL3-20.0 TL3

Authorised electrician

7.2.2 Connecting the PV generator

Connect the PV generator to the 4 DC positive and the 4 DC negative connection plugs on the underside of

the housing (see Figure 8 on page 18). Note the wiring examples given below. The inverter detects these typical

configurations automatically. In individual cases, you need to set the selected DC connection after installation in

the menu.

NOTE

Connected PV modules must be dimensioned for the DC system voltage in accordance with IEC 61730

Class A, but at least for the value of the AC grid voltage

DANGER

Risk of fatal injury due to contact voltages.

During installation: Electrically disconnect the DC positive and DC negative from the protective

earth (PE).

Removing the plug connection before disconnecting the inverter from the PC generator can result in

a hazard to health and damage to the inverter.

Disconnect the inverter from the PV generator using the integrated DC isolator switch.

Remove the plug connector.

1

A

B

2

3

4

Figure 8: Connections for DC positive and DC negative

Key

A

MPP tracker A

B

MPP tracker B

1.2 DC-Plus/DC-Minus-Connections to MPP tracker A

3.4 DC-Plus/DC-Minus-Connections to MPP tracker B