Isolated 4-20 ma transmitter output, Modbus, Rtu serial communications – Precision Digital PD6000 User Manual

Page 11

Advertising
background image

Model PD6000 Analog Input Process Meter Instruction Manual

11

AUTO
INITIALIZATION

When power is applied to the meter, relays will reflect the
state of the input to the meter.

Isolated 4-20 mA Transmitter Output

OUTPUT
SOURCE

Process variable (PV), max, min, set points 1-8, Modbus
input, or manual control mode

SCALING RANGE 1.000 to 23.000 mA for any display range

CALIBRATION

Factory calibrated: 4.000 to 20.000 = 4-20 mA output

ANALOG OUT
PROGRAMMING

23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break

ACCURACY

± 0.1% of span ± 0.004 mA

TEMPERATURE
DRIFT

0.4 µA/

C max from 0 to 65C ambient,

0.8 µA/

C max from -40 to 0C ambient

Note: Analog output drift is separate from input drift.

ISOLATED
TRANSMITTER
POWER SUPPLY

Terminals I+ & R: 24 VDC

 5% @ 40 mA maximum; may

be used to power the 4-20 mA output or other devices.
Refer to Figure 5 on page 18 and Figure 13 on page 22.

EXTERNAL LOOP
POWER SUPPLY

35 VDC maximum

OUTPUT LOOP
RESISTANCE

Power supply

Minimum

Maximum

24 VDC

10

 700

35 VDC (external)

100

 1200

Modbus

®

RTU Serial Communications

SLAVE ID

1 – 247 (Meter address)

BAUD RATE

300 – 19,200 bps

TRANSMIT
TIME DELAY

Programmable between 0 and 199 ms
or transmitter always on for RS-422 communication

DATA

8 bit (1 start bit, 1 or 2 stop bits)

PARITY

Even, Odd, or None with 1 or 2 stop bits

BYTE-TO-BYTE
TIMEOUT

0.01 – 2.54 second

TURN AROUND
DELAY

Less than 2 ms (fixed)

Note: Refer to the PD6000/PD7000 Modbus Register Tables located at
www.predig.com for details.

Advertising
This manual is related to the following products: